Rheem M8350ti Installation Instructions - Page 9

Water Connections, Pressure Drop - model

Page 9 highlights

Model No. 5350 6350/6350HC 8350 VAC in - Phase - Hz 208/230 - 1 - 60 208/230 - 1 - 60 208/230 - 1 - 60 208/230 - 3 - 60 Minimum Circuit Ampacity (A) 40.0 42.0 42.0 34.0 Maximum Breaker Size (A) 60 60 60 50 Table A: Typical System Electrical Power Requirements This unit is pre-wired to work with external control systems, heat-on-demand options and other external time clock overrides. Refer to the external control system's instructions, and page 26 of this manual, for installation information. the purpose and, in either case, should be at least equal in size to the main pool/spa circulation piping. Water Connections CAUTION: The heat pump pool heater inlet and outlet connections are NOT interchangeable. They must be connected as instructed below. WATER IN WATER OUT 1. Connect the heat pump pool heater in the return water line between the filter and the pool/spa. See the Plumbing Diagrams beginning on page 16. 2. Connect the filter outlet to the fitting marked WATER IN at the bottom front of the unit. 3. Connect the fitting marked WATER OUT to the return piping to the pool/spa. Unit inlet/outlet connection fittings are 2-inch PVC unions. Fig. 2: Water Connections 4. In cold weather (freeze zone) areas, shutoff valves (ball or gate type) must be installed at the unit inlet and outlet to facilitate service and cold weather drain-down. 5. Operate the pump and check the system for leaks. Pressure Drop Water connections from the unit to the main return For system pressure drop information, refer to Table B line can be PVC pipe or flexible pipe approved for below. Flow (gpm) 30 40 50 60 70 80 5350 4 7 10 11 12 13 Pressure Drop (psi) 6350/6350HC 6 9 10 11 12 13 8350 9 9 10 11 12 13 Note: Multiply the pressure drop in psi by 2.3067 to yield the pressure drop in Ft. H2O Head (TDH). Table B: Pressure Drop Across Heat Pump Pool Heater 9

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28

9
This unit is pre-wired to work with external control sys-
tems, heat-on-demand options and other external time
clock overrides. Refer to the external control system’s
instructions, and page 26 of this manual, for installa-
tion information.
Water Connections
1.
Connect the heat pump pool heater in the return
water line between the filter and the pool/spa. See
the
Plumbing Diagrams
beginning on page 16.
2.
Connect the filter outlet to the fitting marked
WATER IN
at the bottom front of the unit.
3.
Connect the fitting marked
WATER OUT
to the
return piping to the pool/spa. Unit inlet/outlet con-
nection fittings are 2-inch PVC unions.
Water connections from the unit to the main return
line can be PVC pipe or flexible pipe approved for
the purpose and, in either case, should be at least
equal in size to the main pool/spa circulation pip-
ing.
4.
In cold weather (freeze zone) areas, shutoff valves
(ball or gate type) must be installed at the unit inlet
and outlet to facilitate service and cold weather
drain-down.
5.
Operate the pump and check the system for leaks.
Pressure Drop
For system pressure drop information, refer to Table B
below.
CAUTION:
The heat pump pool heater inlet and
outlet connections are
NOT
interchangeable. They
must be connected as instructed below.
Fig. 2: Water Connections
WATER IN
WATER OUT
Table B: Pressure Drop Across Heat Pump Pool Heater
Flow
(gpm)
Pressure Drop (psi)
5350
6350/6350HC
8350
30
4
6
9
40
7
9
9
50
10
10
10
60
11
11
11
70
12
12
12
80
13
13
13
Model No.
VAC in - Phase - Hz
Minimum Circuit
Ampacity (A)
Maximum Breaker
Size (A)
5350
208/230 - 1 - 60
40.0
60
6350/6350HC
208/230 - 1 - 60
42.0
60
8350
208/230 - 1 - 60
42.0
60
208/230 - 3 - 60
34.0
50
Table A: Typical System Electrical Power Requirements
Note: Multiply the pressure drop in psi by 2.3067 to yield the pressure drop in Ft. H
2
O Head (TDH).