Toshiba UT1A1A010C6 User Guide - Page 34
Front Panel Settings
View all Toshiba UT1A1A010C6 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 34 highlights
5.5 Front Panel Settings Listed below are the default settings of the primary UPS parameters. Settings 1) O/P VOLT SET (output voltage set) Options 100/110/115/120/127 208/220/230/240 Vac 2) I/P FREQ SET (input frequency setting) 3) I/P BYPASS SET (input bypass setting) 4) FREE RUN SET +/- 2% +/- 5% +/- 7% +/- 10% +10% -15% +15% -20% ON/OFF 5) HE MODE SET ON/OFF 6) MANUAL BYPASS ON/OFF Default 120 V 230 V Remarks 120 V (FOR LV series) 230 V (FOR HV series) +/- 5% +10% -15% Input Frequency range in Free Run mode Input Voltage range when Bypass mode is on ON OFF OFF If ON, enable UPS runs on Asynchronous mode. For example: If input freq 55Hz output freq stays at 60Hz. If OFF, disable UPS runs on synchronous mode. For example: If input freq 55Hz, UPS will go to battery mode. If ON, enable UPS runs in High efficiency mode. The unit will be in bypass mode with 95% or higher efficiency. If OFF, the unit will be in the online mode with 85% efficiency. If ON, enable UPS switch to Bypass mode immediately. 12