Toshiba UT1A1A010C6 User Guide - Page 46

Technical Specifications - ut1a1a020c6

Page 46 highlights

9. Technical Specifications 9.1 Power Range 1000-3000 VA (120 V) Tower Rackmount (2U) Input Output Battery Physical Environment Warranty US 120V Model US 120V Model Voltage Voltage Range Frequency Power Factor Topology Voltage Capacity (VA) Capacity (W) Frequency Wave Form Load Power Factor Efficiency AC/DC/AC Rated Current Overload Capacity Crest Factor DC Voltage (Tower & 2U) Backup Time (Tower & 2U) Interface Dimensions (Tower) Dimensions (2U) Weight (Tower/2U) Line Cord Receptacles (Tower/2U) Operating Temperature Altitude UT1A1A010C6 UT1A1A015C6 UT1A1A020C6 UT1A1A030C6 UT1A1A010C6R UT1A1A015C6R UT1A1A020C6R UT1A1A030C6R KB2 KB2 KB2 KB2 1000 VA 700 W 120 VAC (80 - 144 V) +20% to -33% 50 / 60 Hz auto sensing Greater than 0.97 True on-line Double conversion Input PF correction 120 VAC 1500 VA 2000 VA 1050 W 1400 W 50 / 60 Hz auto sensing * Sine wave, zero transfer time 0.70 3000 VA 2100 W Greater than 86% Greater than 85% 8.3 A 12.5 A 16.6 A 25 A 125% for 1 min 150% for 10 sec 125% for 1 min 130% for 10 sec 3.0 at full load 2.5 at full load 36 V / 12 V 72V / 12 V 72V / 12 V 9 AH x 3 7.2 AH x 6 9 AH x 6 7 min 6 min 6 min 5 min (full load) (full load) (full load) (full load) RS-232 and USB standard RemotEye II® and EMD option 16.5"L x 6.0"W x 9.4"H 16.7"L x 8.9"W x 14.2"H 16.7"L x 16.9"W x 3.5"H 25.0"L x 16.9"W x 3.5"H 35.6 lbs / 37.4 lbs / 37.6 lbs 37.6 lbs 5-15P NEMA 5 - 15 P (6 / 6) 68.4 lbs / 72.6 lbs / 69.5 lbs 71.5 lbs 5-20P L5-30P NEMA 5-15 P (12 / 4) 32 - 104°F (0 - 40°C) 11500 ft (3500 m) above sea level Three years on electronics Two years full replacement on battery (See Toshiba warranty policy for full details.) • Output frequency can hard set at 50 or 60 Hz by installing an optional software upgrade. This upgrade enables the user to select a fixed output frequency and simultaneously disables the bypass mode. Standards - Safety: EN50091-1-1, Emissions: EN50091-2, Immunity: EN50091-2 B (1000-1500 VA) 24

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51

24
9. Technical Specifications
9.1
Power Range 1000-3000 VA (120 V)
Tower
US 120V
Model
UT1A1A010C6
UT1A1A015C6
UT1A1A020C6
UT1A1A030C6
Rack-
mount
(2U)
US 120V
Model
UT1A1A010C6R
KB2
UT1A1A015C6R
KB2
UT1A1A020C6R
KB2
UT1A1A030C6R
KB2
Input
Voltage
120 VAC (80 – 144 V)
Voltage Range
+20% to -33%
Frequency
50 / 60 Hz auto sensing
Power Factor
Greater than 0.97
Topology
True on-line Double conversion Input PF correction
Output
Voltage
120 VAC
Capacity (VA)
1000 VA
1500 VA
2000 VA
3000 VA
Capacity (W)
700 W
1050 W
1400 W
2100 W
Frequency
50 / 60 Hz auto sensing *
Wave Form
Sine wave, zero transfer time
Load Power
Factor
0.70
Efficiency
AC/DC/AC
Greater than 86%
Greater than 85%
Rated Current
8.3 A
12.5 A
16.6 A
25 A
Overload
Capacity
125% for 1 min 150% for 10 sec
125% for 1 min
130% for 10 sec
Crest Factor
3.0 at full load
2.5 at full load
Battery
DC Voltage
(Tower & 2U)
36 V / 12 V
9 AH x 3
72V / 12 V
7.2 AH x 6
72V / 12 V
9 AH x 6
Backup Time
(Tower & 2U)
7 min
(full load)
6 min
(full load)
6 min
(full load)
5 min
(full load)
Interface
RS-232 and USB standard RemotEye II® and EMD option
Physical
Dimensions
(Tower)
16.5”L x 6.0”W x 9.4”H
16.7"L x 8.9"W x 14.2"H
Dimensions
(2U)
16.7”L x 16.9”W x 3.5”H
25.0"L x 16.9"W x 3.5"H
Weight
(Tower/2U)
35.6 lbs /
37.6 lbs
37.4 lbs /
37.6 lbs
68.4 lbs /
69.5 lbs
72.6 lbs /
71.5 lbs
Line Cord
5-15P
5-20P
L5-30P
Receptacles
(Tower/2U)
NEMA 5 - 15 P (6 / 6)
NEMA 5-15 P (12 / 4)
Environ-
ment
Operating
Temperature
32 – 104
°
F (0 – 40
°
C)
Altitude
11500 ft (3500 m) above sea level
Warranty
Three years on electronics
Two years full replacement on battery (See Toshiba warranty policy for full details.)
Output frequency can hard set at 50 or 60 Hz by installing an optional software upgrade.
This upgrade enables the user
to select a fixed output frequency and simultaneously disables the bypass mode.
Standards - Safety: EN50091-1-1, Emissions: EN50091-2, Immunity: EN50091-2 B (1000-1500 VA)