ENGLISH 2. Presentation In/Out settings ON/OFF settings Battery settings Description Load segments - Auto shutdown delay Overload prealarm Cold start Forced reboot Auto restart Energy saving Sleep mode Remote command RPO delay Automatic battery test Low battery warning Restart battery level Battery charge mode Deep discharge protection Available settings Default settings [Disable] [0s] [1 s] [2 s]...[65354 s] Group 1: Disable During a power outage, Group 2: Disable authorizes UPS to turn off power to equipment connected to Group 1 and/or Group 2 outlets. This feature allows the shedding of non-critical loads in order to conserve battery power for critical loads connected to the Primary group. [10 %] [15 %] [20 %] ... [100 %] [105 %] [105 %] Sets critical percentage of load where alarm overload alarm occurs. [Disable] [Enable] Enable Enables the product to be started on battery power. First cold start isw always disabled. [Disable] [Enable] Enable If mains recover during a shutdown sequence: - if enabled, shutdown sequence will complete and wait 10 seconds prior to restart - if disabled, shutdown sequence will not complete and restart will occur immediately. [Disable] [Enable] Enables the product to restart automatically when mains recovers after a complete battery discharge. Enable [Disable] [Enable] If enabled, UPS will shutdown after 5 min. of back-up time, if no load is detected on the output. Disable [Disable] [Enable] If disabled, LCD and communication will turn OFF immediately after UPS is OFF. If enabled, LCD and communication stays ON 1h30 min after UPS is OFF. Disable [Disable] [Enable] Enable If enabled, shutdown or restart commands from software are authorised. [0 s] [1s ] [2 s]...[180 s] [0 s] Delays remote power off command [No test] [Every day] [Every week] Every week [Every month] (in constant charge) Available only if battery charge mode otherwise following ABM is set to constant charge. [1 %] [2 %] ... [100 %] 20 % The alarm triggers when the set percentage of battery capacity is reached during a back-up time. [1 %] [2 %] ... [100 %] 0 % If set, automatic restart will occur only when percentage of battery charge is reached. [ABM cycling] [Constant charge] ABM cycling [Yes] [No] Yes If set to Yes, the UPS automatically prevents battery from deep discharge by adapting end of back-up time voltage threshold. 620-00082-01-us (en) Page 13

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28

Page 13
620-00082-01-us (en)
ENGLISH
2. Presentation
Description
Available settings
Default settings
In/Out settings
Load segments
- Auto shutdown
delay
[Disable] [0s] [1 s] [2 s]…[65354 s]
During a power outage,
authorizes UPS to turn off power to
equipment connected to Group 1
and/or Group 2 outlets.
This feature allows the shedding of
non-critical loads in order to conserve
battery power for critical loads
connected to the Primary group.
Group 1: Disable
Group 2: Disable
Overload
prealarm
[10 %] [15 %] [20 %] ... [100 %] [105 %]
Sets critical percentage of load where
alarm overload alarm occurs.
[105 %]
ON/OFF settings
Cold start
[Disable] [Enable]
Enables the product to be started on
battery power.
First cold start isw always disabled.
Enable
Forced reboot
[Disable] [Enable]
If mains recover during a shutdown
sequence:
- if enabled, shutdown sequence will
complete and wait 10 seconds prior
to restart
- if disabled, shutdown sequence will
not complete and restart will occur
immediately.
Enable
Auto restart
[Disable] [Enable]
Enables the product to restart
automatically when mains recovers
after a complete battery discharge.
Enable
Energy saving
[Disable] [Enable]
If enabled, UPS will shutdown after
5 min. of back-up time, if no load is
detected on the output.
Disable
Sleep mode
[Disable] [Enable]
If disabled, LCD and communication
will turn OFF immediately after UPS
is OFF.
If enabled, LCD and communication
stays ON 1h30 min after UPS is OFF.
Disable
Remote command
[Disable] [Enable]
If enabled, shutdown or restart
commands from software are
authorised.
Enable
RPO delay
[0 s] [1s ] [2 s]...[180 s]
Delays remote power off command
[0 s]
Battery settings
Automatic battery
test
[No test] [Every day] [Every week]
[Every month]
Available only if battery charge mode
is set to constant charge.
Every week
(in constant charge)
otherwise following ABM
Low battery
warning
[1 %] [2 %] ... [100 %]
The alarm triggers when the set
percentage of battery capacity is
reached during a back-up time.
20 %
Restart battery
level
[1 %] [2 %] ... [100 %]
If set, automatic restart will occur
only when percentage of battery
charge is reached.
0 %
Battery charge
mode
[ABM cycling] [Constant charge]
ABM cycling
Deep discharge
protection
[Yes] [No]
If set to Yes, the UPS automatically
prevents battery from deep discharge
by adapting end of back-up time
voltage threshold.
Yes