Tripp Lite 5P1500 Eaton 5P UPS Installation and User Manual - Page 25
Appendices
View all Tripp Lite 5P1500 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 25 highlights
ENGLISH 6.1 Technical specifications Filter Transformer "AVR" Charger Inverter 6. Appendices Battery Tower Rack Output Power @ 120 V Output Power capacity @ 125 V Output Power @ 100 V AC Input power • Rated input voltage • Input voltage range • Input frequency range Output on battery power • Voltage • Frequency Battery (sealed lead acid, maintenance free) • Standard 5P 550 R 550 VA 420 W 550 VA 420 W 458 VA 350 W 5P 750 5P 750 R 750 VA 600 W 750 VA 600 W 625 VA 500 W 5P 1000 5P 1000 R 1000 VA 770 W 1000 VA 770 W 833 VA 641 W 5P 1500 5P 1500 R 1440 VA 1100 W 1440 VA 1100 W 1080 VA 825 W Single phase 100-125 V 80 to 162 V (1) 47 to 70 Hz (50 Hz system), 56.5 to 70 Hz (60 Hz system) (2) 100/120 V (-10/+6 %) (3) 50/60 Hz ±0.1 Hz Tower 2 x 12 V 7 Ah 2 x 12 V 9 Ah 3 x 12 V 9 Ah Environment • Operating temperature range • Storage temperature range • Relative humidity 2 x 6 V 9 Ah 4 x 6 V 7 Ah Rack 4 x 6 V 9 Ah 0 to 35 °C -15 to +50 °C 0 to 90 % (without condensation) • Noise level < 40 dBA (1) The high and low thresholds can be adjusted using UPS settings. (2) Up to 40 Hz in low -sensitivity mode (programmable using UPS settings). (3) Adjustable to 100/120/125 V, must be set to the identical AC power source value. 6 x 6 V 9 Ah 0 to 40 °C For 5P Models - "CAUTION - To reduce the risk of fire, connect only to a circuit provided with 20 amperes maximum branch circuit overcurrent protection in accordance with the National Electric Code, ANSI/NFPA 70". This product is designed for IT power distribution system. 620-00082-01-us (en) Page 25