5. Maintenance 5.1 Troubleshooting Operation status Batteries disconnected Overload Possible cause The UPS does not recognize the internal batteries The batteries are disconnected Power requirements exceeds the UPS capacity (greater than 105 % of nominal) Action If the condition persists, contact your service representative Verify that all batteries are properly connected. If the condition persists, contact your service representative. Remove some of the equipment from the UPS. The UPS continues to operate, but may shutdown if the load increases. The alarm resets when the condition becomes inactive. End of battery life The end of the battery life is reached. Contact your service representative for battery replacement. Event UPS fault An UPS event occurs Example: Remote Power OFF, the RPO contact has been activated to shutdown the UPS and now prevents restart. The UPS has an internal fault. Set the contact back to its normal position and press button to restart. The UPS does not protect the equipment anymore. Note. the alarm message and the UPS Serial Number, then contact your service representative. 5P 750VA-1.5 KVA US_EN Page 19

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23

Page 19
5P 750VA-1.5 KVA US_EN
5. Maintenance
5.1 Troubleshooting
Operation status
Possible cause
Action
Batteries disconnected
The UPS does not recognize the internal batteries
If the condition persists, contact your
service representative
The batteries are disconnected
Verify that all batteries are properly
connected. If the condition persists,
contact your service representative.
Overload
Power requirements exceeds the
UPS capacity (greater than 105 %
of nominal)
Remove some of the equipment from
the UPS. The UPS continues to
operate, but may shutdown if the load
increases. The alarm resets when the
condition becomes inactive.
End of battery life
The end of the battery life is reached.
Contact your service representative
for battery replacement.
Event
An UPS event occurs
Example:
Remote Power OFF, the RPO
contact has been activated to
shutdown the UPS and now
prevents restart.
Set the contact back to its normal
position and press
button to
restart.
UPS fault
The UPS has an internal fault.
The UPS does not protect the
equipment anymore.
Note. the alarm message and
the UPS Serial Number, then contact
your service representative.