Tripp Lite B098016 Owners Manual for B093- B097- and B098-Series Console Serve - Page 132
UPS/Power Supply, 2.4 UPS Status
View all Tripp Lite B098016 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 132 highlights
7. Alerts, Auto-Response and Logging 7.2.3 UPS/Power Supply To use the properties of any attached UPS as the trigger event: • Click on UPS / Power Supply as the Check Condition. • Select UPS Power Device Property (Input Voltage, Battery Charge %, Load %, Input Frequency Hz or Temperature in °C) that will checked for the trigger. • Specify the Trigger value that the check measurement must exceed or drop below in order to trigger the auto-response. • Select Comparison type as being Above Trigger Value or Below Trigger Value to trigger. • Specify any Hysteresis factor that is to be applied to environmental measurements (e.g. if an auto-response was set up with a trigger event of a battery charge below 20% with a hysteresis of 5, then the trigger condition would not be seen as having been resolved until the battery charge was above 25%). • Check Save Auto-Response. Note: Before configuring UPS checks in auto-response, you first must configure the attached UPS. 7.2.4 UPS Status To use the alert state of any attached UPS as the auto-response trigger event: • Click on UPS Status as the Check Condition. • Select the reported UPS State to trigger the auto-response (either On Battery or Low Battery). The auto-response will resolve when the UPS state returns to the "Online" state. • Select which connected UPS Device to monitor and check Save Auto-Response. Note: Before configuring UPS state checks in auto-response, you first must configure the attached UPS. 132