Page 23 highlights

Chapter 6 Specifications 6.1 Product Specifications Table 4. Input Characteristics Capacity VA/Watts Voltage AC AC voltage range AC amps frequency AC input protection Line efficiency at full load BC350R(AG-075C) 350 / 210 3A (1) Thermal breaker 5A >97.4% BCR600(AG-075D) 600/300 120 V 95-145VAC High line set 145V +/- 5% High line reset 140V +/- 5% Low line set 95V +/- 5% Low line reset 100V +/- 5% 5A 50 or 60 Hz +/- 3 Hz (default 60Hz) (1) Thermal breaker 7A >97.91% BC850R(AG-075E) 850/450 7.1A (1) Thermal breaker 10A >97.20% Table 5. Output Characteristics Nominal output voltage AC amps out AC output voltage (Line Mode) AC output voltage (Battery Mode) Output AC waveform (Line Mode) Output AC waveform (Battery Mode) Frequency Transfer time AC to DC BC350R(AG-075C) 2.9A (Nom); 3.7A (Max) BC600R(AG-075D) 120V 5A (Nom) ; 6.3A (Max) BC850R(AG-075E) 7.1A (Nom); 8.9A (Max) 120V (follows input voltage 95-145VAC) 120V Sine wave (AC Mode) Modified sine wave (Battery Mode) 50 or 60 Hz follows the AC input frequency Battery cold start is 60Hz only 4 ~ 6 ms (Max < 10 ms) Tripp Lite Series UPS Systems User Guide 93470A-Rev A 17

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78

Tripp Lite Series UPS Systems User Guide
93470A—Rev A
17
Chapter 6
Specifications
6.1
Product Specifications
Table4.InputCharacteristics
BC350R(AG-075C)
BCR600(AG-075D)
BC850R(AG-075E)
CapacityVA/Watts
350 / 210
600/300
850/450
VoltageAC
120 V
ACvoltagerange
95–145VAC
High line set 145V +/- 5%
High line reset 140V +/- 5%
Low line set 95V +/- 5%
Low line reset 100V +/- 5%
ACamps
3A
5A
7.1A
frequency
50 or 60 Hz +/- 3 Hz (default 60Hz)
ACinputprotection
(1) Thermal breaker 5A
(1) Thermal breaker 7A
(1) Thermal breaker 10A
Line efficiency at full load
>97.4%
>97.91%
>97.20%
Table5.OutputCharacteristics
BC350R(AG-075C)
BC600R(AG-075D)
BC850R(AG-075E)
Nominaloutputvoltage
120V
ACampsout
2.9A (Nom); 3.7A (Max)
5A (Nom) ; 6.3A (Max)
7.1A (Nom); 8.9A (Max)
ACoutputvoltage(Line
Mode)
120V (follows input voltage 95–145VAC)
ACoutputvoltage(Battery
Mode)
120V
OutputACwaveform(Line
Mode)
Sine wave (AC Mode)
OutputACwaveform
(BatteryMode)
Modified sine wave (Battery Mode)
Frequency
50 or 60 Hz follows the AC input frequency
Battery cold start is 60Hz only
TransfertimeACtoDC
4 ~ 6 ms (Max < 10 ms)