Tripp Lite BC350R Owners Manual for BC350R BC600R and BC850R Multi-language - Page 23
Specifications
View all Tripp Lite BC350R manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 23 highlights
Chapter 6 Specifications 6.1 Product Specifications Table 4. Input Characteristics Capacity VA/Watts Voltage AC AC voltage range AC amps frequency AC input protection Line efficiency at full load BC350R(AG-075C) 350 / 210 3A (1) Thermal breaker 5A >97.4% BCR600(AG-075D) 600/300 120 V 95-145VAC High line set 145V +/- 5% High line reset 140V +/- 5% Low line set 95V +/- 5% Low line reset 100V +/- 5% 5A 50 or 60 Hz +/- 3 Hz (default 60Hz) (1) Thermal breaker 7A >97.91% BC850R(AG-075E) 850/450 7.1A (1) Thermal breaker 10A >97.20% Table 5. Output Characteristics Nominal output voltage AC amps out AC output voltage (Line Mode) AC output voltage (Battery Mode) Output AC waveform (Line Mode) Output AC waveform (Battery Mode) Frequency Transfer time AC to DC BC350R(AG-075C) 2.9A (Nom); 3.7A (Max) BC600R(AG-075D) 120V 5A (Nom) ; 6.3A (Max) BC850R(AG-075E) 7.1A (Nom); 8.9A (Max) 120V (follows input voltage 95-145VAC) 120V Sine wave (AC Mode) Modified sine wave (Battery Mode) 50 or 60 Hz follows the AC input frequency Battery cold start is 60Hz only 4 ~ 6 ms (Max < 10 ms) Tripp Lite Series UPS Systems User Guide 93470A-Rev A 17