Tripp Lite BP240V500C Owner s Manual for Extended-Run 3-Phase Battery Cabinet - Page 19

connected to the earth ground, nor should it be connected to the neutral of the AC source.

Page 19 highlights

6. Diagrams 6.2.4 +/- 240 VDC (3-Phase) Notes: • All internal wiring is UL-listed, MTW, 105C Hi-Flex cable. • Terminal block is UL-recognized and rated for 600 VDC. • Breaker is UL-listed and rated for 250 A, 600 VDC, 42 KAIC. • Cabinets with breakers are shipped with the breaker in the off/open position and one of the jumper cables disconnected. • Battery arrangements shown are typical but may vary depending on cabinet and battery type. • The "N" center terminal should only be connected to similar terminals on the UPS and any paralleled battery cabinets. It should not be connected to the earth ground, nor should it be connected to the neutral of the AC source. 19

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44

19
6. Diagrams
6.2.4 +/- 240 VDC (3-Phase)
Notes:
• All internal wiring is UL-listed, MTW, 105C Hi-Flex cable.
• Terminal block is UL-recognized and rated for 600 VDC.
• Breaker is UL-listed and rated for 250 A, 600 VDC, 42 KAIC.
• Cabinets with breakers are shipped with the breaker in the off/open position and one of the jumper cables disconnected.
• Battery arrangements shown are typical but may vary depending on cabinet and battery type.
• The “N” center terminal should only be connected to similar terminals on the UPS and any paralleled battery cabinets. It should not be
connected to the earth ground, nor should it be connected to the neutral of the AC source.