Tripp Lite S3M60K60K6T Owners Manual for S3MT-Series 3-Phase 480V-208V and 600 - Page 13
Transformer Cabinet
![]() |
View all Tripp Lite S3M60K60K6T manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 13 highlights
3. Installation 3.7 Transformer-to-UPS Connection Line Diagram Connections are shown below for the cabinet with built-in input isolator transformer, breakers and the red over-temperature LED. Input Transformer Red LED (Lit = Over-Temperature, Off = Normal) AC Input 480V AC Trip Output 208/120V AC, 3-Phase, 4-Wire + Ground to the UPS Input Delta In 480V/208V Wye Breaker 3PH Transformer Cabinet Maintenance Breaker Bypass Breaker PFC Mains Breaker Inverter STS Output 208/120V, 220/127V, 3-Phase, 4-Wire + Ground to Load Output Breaker Charger Battery input: +/-120V DC UPS Figure 3-7: Connection Line Diagram for S3MT-60K480V / S3MT-100K480V 13
![](/manual_guide/products/tripp-lite-s3m100k100k4t-owners-manual-s3mtseries-3phase-480v208v-600v208v-input-transformers-s3mt60k480v-s3mt100k480v-s3mt60k600v-s3mt100k600v-e64328d/13.png)
13
3.7 Transformer-to-UPS Connection Line Diagram
Connections are shown below for the cabinet with built-in input isolator transformer, breakers and the red over-temperature LED.
Figure 3-7: Connection Line Diagram for S3MT-60K480V / S3MT-100K480V
3. Installation
Input Transformer
Red LED (Lit = Over-Temperature, Off = Normal)
Output 208/120V AC,
3-Phase, 4-Wire +
Ground to the UPS Input
Output 208/120V,
220/127V,
3-Phase, 4-Wire +
Ground to Load
Maintenance Breaker
Bypass Breaker
Mains Breaker
Battery input: +/–120V DC
Output Breaker
PFC
STS
Inverter
Charger
Delta In 480V/208V Wye
Transformer Cabinet
UPS
Breaker
3PH
Trip
AC Input 480V AC