Tripp Lite S3M60K60K6T Owners Manual for S3MT-Series 3-Phase 480V-208V and 600 - Page 17

Specifications

Page 17 highlights

5. Specifications Models Description Transformer Type Input Input Voltage Input Voltage Operational Range and De-Rating Input Amps Input Connections Input Configuration Input Connection Type Rated AC Input Frequency Frequency Range and Derating Voltage Selection Voltage Drop: Ratio Ouput, No Load to Full Load Inrush Current Input Isolation Output VA Rating Transformer Output Voltage Output Amps Transformer Output Breaker Rating Output Watts Detailed Output Connections Output Connection Type Output Configuration Input Tranformer Output Isolation Operation Over-Temperature Warning LED (Red) Over-Temperature Protection Reset Device Insulation Class Temperature Rise Full Load Efficiency S3MT-60K480V 3-Phase 60k Input Isolation Transformer, Delta 480V/208V Wye S3MT-60K600V S3MT-100K480V 3-Phase 60k Input Isolation Transformer, Delta 600V/208V Wye 3-Phase 100k Input Isolation Transformer, Delta 480V/208V Wye Dry-Type S3MT-100K600V 3-Phase 100k Input Isolation Transformer, Delta 600V/208V Wye 480V 101A ≤900A (10 ms) 600V 480V -45%, +25% at 40 % Load -20%, +25% at 100 % Load 81A 168A 3-Wire (L1, L2, L3, +PE) Delta Copper Bar 50/60 Hz 40~70 Hz No ≤ 3% ≤710A (10 ms) ≤3330A (10 ms) Yes 600V 134A ≤1160A (10 ms) 60kVA 250A 60,000W 225A 60kVA 100kVA 208/120V, (3-Phase, 4-Wire) 250A 400A 60,000W 100,000W 4-Wire (L1, L2, L3, +PE, +N) Copper Bar Wye Yes 374A 100kVA 400A 100,000W Turns ON at 160°C ±5°C, i.e. a range of 155°C to 165°C ( 311°F to 329°F) Turns OFF at 125°C ±5°C, i.e. a range of 120°C to 130°C (248°F to 266°F) Transformer output turns OFF at temperatures of 160°C ±5°C, i.e. a range of 155°C to 165°C (311°F to 329°F). The transformer output breaker can be turned ON manually when the warning light turns OFF. 180°C 125°C 96.50% 96.70% 17

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60

17
5. Specifications
Models
S3MT-60K480V
S3MT-60K600V
S3MT-100K480V
S3MT-100K600V
Description
3-Phase 60k
Input Isolation
Transformer, Delta
480V/208V Wye
3-Phase 60k
Input Isolation
Transformer, Delta
600V/208V Wye
3-Phase 100k
Input Isolation
Transformer, Delta
480V/208V Wye
3-Phase 100k
Input Isolation
Transformer, Delta
600V/208V Wye
Transformer Type
Dry-Type
Input
Input Voltage
480V
600V
480V
600V
Input Voltage Operational Range and
De-Rating
-45%, +25% at 40 % Load
-20%, +25% at 100 % Load
Input Amps
101A
81A
168A
134A
Input Connections
3-Wire (L1, L2, L3, +PE)
Input Configuration
Delta
Input Connection Type
Copper Bar
Rated AC Input Frequency
50/60 Hz
Frequency Range and Derating
40~70 Hz
Voltage Selection
No
Voltage Drop: Ratio Ouput,
No Load to Full Load
3%
Inrush Current
900A (10 ms)
710A (10 ms)
3330A (10 ms)
1160A (10 ms)
Input Isolation
Yes
Output
VA Rating
60kVA
60kVA
100kVA
100kVA
Transformer Output Voltage
208/120V, (3-Phase, 4-Wire)
Output Amps
225A
374A
Transformer Output Breaker Rating
250A
250A
400A
400A
Output Watts Detailed
60,000W
60,000W
100,000W
100,000W
Output Connections
4-Wire (L1, L2, L3, +PE, +N)
Output Connection Type
Copper Bar
Output Configuration
Wye
Input Tranformer Output Isolation
Yes
Operation
Over-Temperature Warning LED (Red)
Turns ON at 160°C ±5°C, i.e. a range of 155°C to 165°C ( 311°F to 329°F)
Turns OFF at 125°C ±5°C, i.e. a range of 120°C to 130°C (248°F to 266°F)
Over-Temperature Protection
Reset Device
Transformer output turns OFF at temperatures of 160°C ±5°C,
i.e. a range of 155°C to 165°C (311°F to 329°F).
The transformer output breaker can be turned ON manually when the
warning light turns OFF.
Insulation Class
180°C
Temperature Rise
125°C
Full Load Efficiency
96.50%
96.70%