Multiple Transformer Connections
View all Tripp Lite S3M60K60K6T manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 15 highlights
3. Installation 3.8 Multiple Transformer Connections WARNING: The transformer output neutral is not bonded to chassis ground. Please provide a means to connect the transformer chassis ground to the transformer output neutral. Note: The transformer chassis ground must be connected to earth ground. IMPORTANT: You may view and/or download this manual from the tripplite.com website to view the cable connections in colors. 3.8.1 Connections for S3MT-60K480V/S3MT-60K600V to S3M50K or S3M60K UPS Transfomer input is Delta 3-Wire (3Ph + Ground) And transformer output is Wye 4-Wire (3Ph + N + Ground). Figure 3-8: UPS (Rear View) Transformer Cabinet (Front View) 3.8.2 Connections for S3MT-100K480V/S3MT-100K600V to S3M80K or S3M100K UPS Transfomer input is Delta 3-Wire (3Ph + Ground) And transformer output is Wye 4-Wire (3Ph + N + Ground). Figure 3-9: UPS (Rear View) Transformer Cabinet (Front View) 15