Output Settings
View all Tripp Lite SU6000RT4UHV manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 22 highlights
Operation (continued) Output Settings Note: Any Output Setting changes require a UPS power cycle. Output Voltage: Used to set the UPS' output voltage rating. From the SETUP MENU screen, scroll DOWNi until you reach the OUTPUT SETTING screen. Press ON to reach an OUTPUT VOLTAGE screen and ON again. You can now scroll DOWNi or UPh between 5 voltage values: 200/208/220/230/240V. Press ON to save your desired voltage. DEFAULT is set to 208V. OUTPUT SETTING ENT DOWN UP OUTPUT VOLTAGE ENT DOWN UP To ENTER *230V* ENT DOWN UP 220V ENT DOWN UP 208V ENT DOWN UP 200V ENT DOWN UP 240V ENT DOWN UP Frequency Converter: Used to set the Frequency Converter Mode. From the SETUP MENU screen, scroll DOWNi until you reach the OUTPUT SETTING screen. Press ENTER for the OUTPUT VOLTAGE screen and DOWNi to access the FREQ CONVERTER screen. Here, press ON. Now you can scroll DOWNi or UPh between DISABLE, 50 and 60 Hz. Press ON to save your selection. When on DISABLE, the UPS will automatically detect input frequency and select 50 or 60 Hz accordingly. The DEFAULT selection is DISABLE. OUTPUT SETTING ENT DOWN UP OUTPUT VOLTAGE ENT DOWN UP To ENTER FREQ. CONVERTER ENT DOWN UP *DISABLE* ENT DOWN UP 50Hz ENT DOWN UP 60Hz ENT DOWN UP 22 201207113 933070.indb 22 9/17/2012 1:20:08 PM