5.3. External Relay Speed Control Wiring (For remote selection of pump speed) Note: For third party controls and Hayward controls that are NOT software compatible. Figure 5.3-1 Connection wire must be rated for a minimum of 300V. Inputs are rated to accept a low voltage supply of 18-30VAC (24VAC+/-20%) or 9-30VDC (12/24VDC +/-20%). SW200 DIP switch #1 and #2 must be "ON". The TriStar VS pump can be controlled from third party pool controls as well as Hayward controls that are not software compatible using relay contacts to select the speeds set in the Timer Menu (see section 6.7). In addition to this section you may also consult the applicable pool control installation manual for electrical connection details. Once installed, Remote Control Mode must be set to Relay Control in the pump Configuration Menu (see section 6.6). Preset Speeds 1-4 and Quick Clean are disabled when the pump is remotely controlled. When inputs STEP 1-3 are activated via the pool control relay contacts, timer speeds 1-8 are selected according to the following table (see section 6.7): Timer Speed 1 2 3 4 5 6 7 8 STEP 1 Status OFF ON OFF ON OFF ON OFF ON STEP 2 Status OFF OFF ON ON OFF OFF ON ON STEP 3 Status OFF OFF OFF OFF ON ON ON ON The number of speeds available depends on the number of auxiliary relays used as noted below: 1. Filter pump relay plus 1 auxiliary relays allows control of 2 speeds 2. Filter pump relay plus 2 auxiliary relays allows control of 4 speeds 3. Filter pump relay plus 3 auxiliary relays allows control of 8 speeds Page 16 of 36 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS TriStar VS Pump IS3200VSP Rev-C

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36

USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
Page 16 of 36
TriStar VS Pump
IS3200VSP
Rev-C
5.3.
External Relay Speed Control Wiring (For remote selection of pump speed)
Note:
For third party controls and Hayward controls that are NOT software compatible.
Figure 5.3-1
Connection wire must be rated for a minimum of 300V.
Inputs are rated to accept a low voltage supply of 18-30VAC
(24VAC+/-20%) or 9-30VDC
(12/24VDC +/-20%). SW200 DIP switch #1 and #2 must be “ON”.
The TriStar VS pump can be controlled from third party pool controls as well as Hayward controls that are not
software compatible using relay contacts to select the speeds set in the Timer Menu (see section 6.7).
In addition to
this section you may also consult the applicable pool control installation manual for electrical connection details.
Once installed, Remote Control Mode must be set to Relay Control in the pump Configuration Menu (see section 6.6).
Preset Speeds 1-4 and Quick Clean are disabled when the pump is remotely controlled.
When inputs STEP 1-3 are
activated via the pool control relay contacts, timer speeds 1-8 are selected according to the following table (see
section 6.7):
Timer
Speed
STEP 1
Status
STEP 2
Status
STEP 3
Status
1
OFF
OFF
OFF
2
ON
OFF
OFF
3
OFF
ON
OFF
4
ON
ON
OFF
5
OFF
OFF
ON
6
ON
OFF
ON
7
OFF
ON
ON
8
ON
ON
ON
The number of speeds available depends on the number of auxiliary relays used as noted below:
1.
Filter pump relay plus 1 auxiliary relays allows control of 2 speeds
2.
Filter pump relay plus 2 auxiliary relays allows control of 4 speeds
3.
Filter pump relay plus 3 auxiliary relays allows control of 8 speeds