HP Integrity Superdome SX2000 User Guide, Sixth Edition - HP Integrity Superdo - Page 150
Cooling Requirements, Basic Air Conditioning Equipment Requirements, Air filtration
View all HP Integrity Superdome SX2000 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 150 highlights
Site Preparation Electrical and Environmental Guidelines • Ensure a minimum ceiling height of 12 inches between the top of the server and the ceiling. Ensure all ceiling clips are in place. Cooling Requirements Air conditioning equipment requirements and recommendations are described in the following sections. Basic Air Conditioning Equipment Requirements The cooling capacity of the installed air conditioning equipment for the computer room should be sufficient to offset the computer equipment dissipation loads, as well as any space envelope heat gain. This equipment should include: • Air filtration • Cooling or dehumidification • Humidification • Reheating • Air distribution • System controls adequate to maintain the computer room within the operating ranges listed in Table 5-1. 138 Chapter 5