HP Integrity rx8620 Site Preparation Guide, Fourth Edition - HP Integrity rx86 - Page 16

Acoustic Noise Specification, Air Flow

Page 16 highlights

System Specifications Environmental Specifications Acoustic Noise Specification The acoustic noise specification for the HP Integrity rx8620 Server is 55.6 db (sound pressure level at bystander position). It is appropriate for dedicated computer room environments, not office environments. The LwA is 7.4 Bels. Care should be taken to understand the acoustic noise specifications relative to operator positions within the computer room or when adding servers to computer rooms with existing noise sources. Air Flow The recommended HP Integrity rx8620 Server cabinet air intake temperature is between 68° F and 77° F (20° C and 25° C) at 960 CFM. Figure 1-1 illustrates the location of the inlet and outlet airducts on a single cabinet. Air is drawn into the front of the HP Integrity rx8620 Server and forced out the rear. Figure 1-1 Airflow Diagram 10 Chapter 1

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68

Chapter 1
System Specifications
Environmental Specifications
10
Acoustic Noise Specification
The acoustic noise specification for the HP Integrity rx8620 Server is 55.6 db (sound pressure level at
bystander position). It is appropriate for dedicated computer room environments, not office environments.
The LwA is 7.4 Bels. Care should be taken to understand the acoustic noise specifications relative to operator
positions within the computer room or when adding servers to computer rooms with existing noise sources.
Air Flow
The recommended HP Integrity rx8620 Server cabinet air intake temperature is between 68
°
F and 77
°
F (20
°
C and 25
°
C) at 960 CFM.
Figure 1-1 illustrates the location of the inlet and outlet airducts on a single cabinet. Air is drawn into the
front of the HP Integrity rx8620 Server and forced out the rear.
Figure 1-1
Airflow Diagram