HP R/T2200 IEC-320-C14 HP Power Protector User Guide - Page 84
Configuring the redundantly powered HPPP Client power source
View all HP R/T2200 IEC-320-C14 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 84 highlights
Configuring the redundantly powered HPPP Client power source To configure the power source of redundantly powered HPPP Clients: 1. Open the HPPP Client web interface. 2. Select Settings, and then select Device Discovery. 3. Select a redundant power source from the Node List, and then click Configure power source. The Powersource Configuration screen appears. 4. Enter values in the Source #1 configuration fields, and then select the Is this machine protected by redundancy check box. 5. Enter values in the Source #2 configuration fields, and then click Save. 6. Select Settings and Shutdown Parameters, and then select Edit shutdown configuration. 7. Enter a value in the Shutdown initiated after (sec) field. IMPORTANT: A Client Shutdown initiated after value of none automatically sets the shutdown value of any UPS Network Modules to the default 99999 seconds upon reset. In this configuration, UPS devices power down as late as possible without performing a graceful shutdown. To configure graceful shutdowns, enter the value for the Client, reset the system, and then enter a value in the Shutdown initiated after (sec) field of any UPS Network Modules. The Client uses the greatest value of any configured HPPP devices to perform a graceful shutdown when one of the redundant UPS devices goes on battery. Configuration and operation 84