Wiring Diagrams I Main PCB CN29 TO INVERTER BOARD (INVERTER PCB COMMUNICATION TERMINAL) CN38 EEV-OUT (OUTDOOR ELECTRONIC EXPANSION VALVE) CN40 EEV-SC (SUBCOOLING CIRCUIT ELECTRONIC EXPANSION VALVE) CN44 P(I) S/W (INV COMP HIGH PRESSUR SWITCH)) CN43 P(C) S/W (CONSTANT COMP HIGH PRESSURE SWITCH) CN17 LIQ(C) (CONSTANT COMP LIQUID VALVE CN16 LIQ(I) (INVERTER COMP LIQUID VALVE CN15 AC FAN (AC FAN POWER SUPPLY) CN14 MAGNET(C) (CONSTANT COMP MAGNETIC SWITCH) CN13 HOT GAS (HOT GAS SOLENOID VALVE) CN11 HEATER(C) (CONSTANT COMP HEATER) CN10 HEATER(I) (INVERTER COMP HEATER) CN09 4WAY (4 WAY REVERSING VALVE) CN08 AC 220 V (220 V POWER INPUT TERMINAL) JIG1, JIG2 (JIG POWER TERMINAL : AC 220V) CN27 STD_COMP CT1 (CONSTANT COMP CURRENT SENSOR) CN32 P-SENSOR(L) (LOW PRESSURE SENSOR) SW01S RESET (RESET BUTTON) CN04 FLASH_WRITE (ONBOARDING TERMINAL) CN05 TO JIG (JIG CONNECTION TERMINAL: LGMV) SW02V AUTO ADDRES (AUTO ADDRESSING SWITCH) CN41 CEN CONTROL (CENTRAL CONTROL TERMINAL) CN33 SC-OUT (SC CIRCUIT OUTLET TEMP SENSOR) SC-IN (SC CIRCUIT INTLET TEMP SENSOR) SUCTION (SUCTION TEMPERATURE SENSOR) CN34 DISCHARGE(I) (INV DISCHARGE TEMP SENSOR) HEX1 (OUTDOOR HEX TEMP SENSOR 1) HEX2 (OUTDOOR HEX TEMP SENSOR 2) CN35 AIR (OUTDOOR TEMPERATURE SENSOR) SUCTION (SUCTION TEMPERATURE SENSOR) DISCHARGE(C) (CONST COMP DISCHARGE TEMP SENSOR) CN30 P-SENSOR(H) (HIGH PRESSURE SENSOR) Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes - 14 - LGE Internal Use Only