LG HBLG6000R Service Manual - Page 21

Possible Trouble 2, Possible Trouble 3, Possible Trouble 4

Page 21 highlights

Possible Trouble 2 • The compressor does not operate. Is Temp. setting set lower than Room NO Temp.-0.5°C? • Set the Temp. setting to higher Temp. YES Is the voltage No.10 NO of IC01M 0V? YES • Check the RY-COMP. • Check the wiring Diagram. Is the voltage N0.7 of NO IC01M DC 5V? YES • Exchange IC01M. Possible Trouble 3 • The compressor always operate. Is the Unit for 3 minutes NO delay? YES • Wait 3 Minutes • Exchange MAIN P.W.B Ass'y. Is the wire connection of NO RY-COMP all right? YES • Check the RY-COMP. • Connect LEAD Wire to RY-COMP again. Possible Trouble 4 • Fan does not operate. Is the voltage NO.1 or 4 NO of IC01M DC 5V? YES Is the voltage NO.13 or 16 NO of IC01M 0V? YES • Check the RY-Hi or RY-Lo. • Check the wiring diagram. -21- • Exchange IC01M. • Exchange IC01M.

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34

21
Is Temp.
setting set lower than Room
Temp.-0.5
°
C?
Is the voltage No.10
of IC01M 0V?
Exchange IC01M.
Set the Temp. setting to higher Temp.
Wait 3 Minutes
Is the Unit for 3 minutes
delay?
Exchange MAIN
P.W.B Ass'y.
Is the voltage N0.7 of
IC01M DC 5V?
Check the RY-COMP.
Check the wiring
Diagram.
NO
NO
NO
NO
YES
YES
YES
YES
Possible Trouble 2
The compressor does not operate.
Is the wire connection of
RY-COMP all right?
Check the RY-COMP.
Connect LEAD Wire to
RY-COMP again.
NO
YES
Possible Trouble 3
The compressor always operate.
Exchange IC01M.
Exchange IC01M.
Is the voltage NO.1 or 4
of IC01M DC 5V?
Is the voltage NO.13 or 16
of IC01M 0V?
Check the RY-Hi or
RY-Lo.
Check the wiring diagram.
NO
NO
YES
YES
Possible Trouble 4
Fan does not operate.