LG WG1005R Owner's Manual - Page 13

Window Requirements

Page 13 highlights

ENGLISH Installation Window Requirements Size This room air conditioner is designed for installation in standard double-hung windows with actual opening widths from 22" to 36". The upper and lower window sash must open sufficiently to allow a clear vertical opening of 15" from the bottom of the upper sash to the window stool. 22" to 36" 15" min (With frame curtain) Sill Interior wall 18 1/2" min. (Without frame curtain) Offset 1/2" to 11/4" Sill Exterior WARNING:This product is a WINDOW AIR CONDITIONER. As such, a standard single-hung or double-hung window is required for proper installation. Non-window installations, including using sleeves, holes in walls, and other installations are not recommended. Select the best location 1. To prevent vibration and noise, make sure the unit is installed securely and firmly 2. Install the unit where the sunlight does not shine directly on the unit. Cooled air 3. The outside of the cabinet must extend outward for at least 11" and there should be no obstacles, such as a fence or wall, within 20" from the back of the cabinet 30"~60" because it will prevent heat radiation of the condenser. Restriction of outside air will greatly reduce the cooling efficiency of the air conditioner. Awning Fence Heat radiation About 1/2" Over 20" Tip! : All side louvers of the cabinet must remain exposed to the outside of the structure. 4. Install the unit a little slanted so the back is slightly lower than the front(about 1/2"). This will force condensed water to flow to the outside. 5. Install the unit with the bottom about 30"~60" above the floor level. Owner's Manual 13

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50

Installation
22" to 36"
Offset
1
/
2
" to 1
1
/
4
"
Sill
Exterior
Interior wall
18
1
/
2
" min.
(Without frame curtain)
S
ill
15" min
(With frame curtain)
Size
This room air conditioner is
designed for installation in standard
double-hung windows with actual
opening widths from 22" to 36".
The upper and lower window sash
must open sufficiently to allow a
clear vertical opening of 15" from the
window stool.
Window Requirements
About
1
/
2
"
30"~60"
Awning
Cooled air
Fence
Over 20"
Heat
radiation
Select the best location
1. To prevent vibration and noise, make sure
the unit is installed securely and firmly
2. Install the unit where the sunlight does not
shine directly on the unit.
3. The outside of the cabinet must extend
outward for at least 11" and there should
be no obstacles, such as a fence or wall,
within 20" from the back of the cabinet
because it will prevent heat radiation of the
condenser.
Restriction of outside air will greatly reduce
the cooling efficiency of the air conditioner.
: All side louvers of the cabinet must remain exposed to the outside of the
structure.
4. Install the unit a little slanted so the back is slightly lower than the front(about
1
/
2
").
This will force condensed water to flow to the outside.
5. Install the unit with the bottom about 30"~60" above the floor level.
WARNING:This product is a WINDOW AIR CONDITIONER. As such,
a standard single-hung or double-hung window is required for proper
installation. Non-window installations, including using sleeves, holes
in walls, and other installations are not recommended.
bottom of the upper sash to the
Tip!
Owner
s Manual
13
ENGLISH