Seagate ST800FM0012 Pulsar.2 SAS Product Manual - Page 57

Seagate ST800FM0012 Manual

Page 57 highlights

11.2 Cooling Cabinet cooling must be designed by the customer so that the temperature of the drive will not exceed temperature conditions specified in Section 7.5.1, "Temperature." The rack, cabinet, or drawer environment for the drive must provide heat removal from the assembly. The system designer should confirm that adequate heat removal is provided using the temperature measurement guidelines described in Section 7.5.1. Forced air flow may be required to keep temperatures at or below the temperatures specified in Section 7.5.1 in which case the drive should be oriented, or air flow directed, so that the least amount of air flow resistance is created while providing air flow. Also, the shortest possible path between the air inlet and exit should be chosen to minimize the travel length of air heated by the drive and other heat sources within the rack, cabinet, or drawer environment. If forced air is determined to be necessary, possible air-flow patterns are shown in Figure 16. The air-flow patterns are created by one or more fans, either forcing or drawing air as shown in the illustrations. Conduction, convection, or other forced air-flow patterns are acceptable as long as the temperature measurement guidelines of Section 7.5.1 are met. Above unit Under unit Note. Air flows in the direction shown (back to front) or in reverse direction (front to back) Above unit Note. Air flows in the direction shown or in reverse direction (side to side) Under unit Figure 16. Air flow Note. Image may not represent actual product, for reference only. Pulsar.2 SAS Product Manual, Rev. B 49

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82

Pulsar.2 SAS Product Manual, Rev. B
49
11.2
Cooling
Cabinet cooling must be designed by the customer so that the temperature of the drive will not exceed temper-
ature conditions specified in Section 7.5.1, "Temperature."
The rack, cabinet, or drawer environment for the drive must provide heat removal from the assembly. The sys-
tem designer should confirm that adequate heat removal is provided using the temperature measurement
guidelines described in Section 7.5.1.
Forced air flow may be required to keep temperatures at or below the temperatures specified in Section 7.5.1
in which case the drive should be oriented, or air flow directed, so that the least amount of air flow resistance is
created while providing air flow. Also, the shortest possible path between the air inlet and exit should be cho-
sen to minimize the travel length of air heated by the drive and other heat sources within the rack, cabinet, or
drawer environment.
If forced air is determined to be necessary, possible air-flow patterns are shown in Figure 16. The air-flow pat-
terns are created by one or more fans, either forcing or drawing air as shown in the illustrations. Conduction,
convection, or other forced air-flow patterns are acceptable as long as the temperature measurement guide-
lines of Section 7.5.1 are met.
Figure 16.
Air flow
Note.
Image may not represent actual product, for reference only.
Above unit
Under unit
Note.
Air flows in the direction shown (back to front)
or in reverse direction (front to back)
Above unit
Under unit
Note.
Air flows in the direction shown or
in reverse direction (side to side)