4.4 User settings The following table displays the options that can be changed by the user. Submenu Available settings Language [English] [Français] [Deutsch] [Español Português] [Italiano] [Simplified Chinese] [Japanese] Menus, status, notices and alarms, UPS fault, Event Log data and settings are in all supported languages. Default settings English Automatic message for user configuration when UPS is powered for the first time. Date / time Local LCD settings Audible alarm Protected access Format: [International] [US] [US] Modify LCD screen brightness and contrast to be adapted to room light conditions. [0] [Enabled] [Disabled on battery] [Always disabled] Enable or disable the buzzer if an alarm occurs. [Enabled] Level: [0-8] [6] [Enabled] [Disabled] Allow the user to lock the settings modification. Password is: 0577 [Disabled] Output voltage Input thresholds In/Out settings Sensitivity Load segments Overload prealarm [100 V] [110 V] [120 V] [125 V] [120 V] [Normal] [Extended] Extended mode authorises lower input voltage (70V) witho ut transferring to battery. This can be used if the load can withstand low voltage supply. [Normal] [High] [Low] Low sensitivity extend the range of input frequency accepted before transferring to battery. [Auto start delay] [High] UPS:[No delay]; Group1:[3s]; Group2:[6s] [Auto shutdown delay] [10%] ... [105%] Load % when overload alarm occurs UPS:[Disabled]; Group1: [Disabled]; Group2:[Disabled] [105%] ON/OFF settings Start/Restart [Cold start] [Auto restart] [Auto start] [Cold start] : ON [Auto restart] : ON [Auto start] : OFF 614-40095-00 21

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42

614-40095-00
21
4.4 User settings
The following table displays the options that can be changed by the user.
Submenu
Available settings
Default settings
Local
settings
Language
[English] [Français] [Deutsch] [Español] [
Русский
]
[Português] [Italiano] [Simplified Chinese] [Japanese]
Menus, status, notices and alarms, UPS fault, Event Log
data and settings are in all supported languages.
English
Automatic message for user
configuration when UPS is
powered for the first time.
Date / time
Format: [International] [US]
[US]
LCD
Modify LCD screen brightness and contrast to be adapted
to room light conditions.
[0]
Audible
alarm
[Enabled] [Disabled on battery] [Always disabled]
Enable or disable the buzzer if an alarm occurs.
[Enabled]
Level: [0-8]
[6]
Protected
access
[Enabled] [Disabled]
Allow the user to lock the settings modification. Password
is: 0577
[Disabled]
In/Out
settings
Output
voltage
[100 V] [110 V] [120 V] [125 V]
[120 V]
Input
thresholds
[Normal] [Extended]
Extended mode authorises lower input voltage (70V)
w
itho
ut transferring to battery.
This can be used if the load can withstand low voltage
supply.
[Normal]
Sensitivity
[High] [Low]
Low sensitivity extend the range of input frequency
accepted before transferring to battery.
[High]
Load
segments
[Auto start delay]
UPS:[No delay]; Group1:[3s];
Group2:[6s]
[Auto shutdown delay]
UPS:[Disabled]; Group1:
[Disabled]; Group2:[Disabled]
Overload
prealarm
[10%] … [105%]
Load % when overload alarm occurs
[105%]
ON/OFF
settings
Start/Restart
[Cold start]
[Auto restart]
[Auto start]
[Cold start] : ON
[Auto restart] : ON
[Auto start] : OFF