Tripp Lite 9PX11KTF11M Eaton 9PX UPS 700-3000 VA 2U Owners Manual
Tripp Lite 9PX11KTF11M Manual
View all Tripp Lite 9PX11KTF11M manuals
Add to My Manuals
Save this manual to your list of manuals |
Tripp Lite 9PX11KTF11M manual content summary:
- Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 1
Copyright © 2016 EATON All rights reserved. 9PX 1-3 KVA US_EN 9PX 700 RT 9PX 1000 RT 9PX 1000GRT 9PX 1500 RT 9PX 1500GRT 9PX 2000 RT 9PX 2200 GRT 9PX 3000 RT 9PX 3000 GRT 9PX 3000 GLRT 9PX EBM 36V RT 9PX EBM 48V RT 9PX EBM 72V RT Installation and user manual ENGLISH - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 2
. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 3
present within the system. It should be opened exclusively by qualified service personnel. • The system must be properly grounded at all times supply circuit). Product safety • To connect the UPS, instructions and operation described in the manual must be followed in the indicated order. • CAUTION - - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 4
SAFETY INSTRUCTIONS Special precautions • The unit is heavy: wear safety shoes and use to contact your EATON representative. • All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the UPS. • For potential safety issue on - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 5
Replacing the UPS equipped with a HotSwap MBP 38 6.6 Recycling the used equipment 38 7. Troubleshooting 7.1 Typical alarms and faults 39 7.2 Silencing the alarm...40 7.3 Service and support...40 7.4 CE compliance contact 40 8. Specifications 8.1 Model specifications 41 9. Glossary 45 Page - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 6
9PX, please read the booklet presenting the safety instructions. Then follow the indications in this manual. To discover the entire range of EATON products of life EATON will process products at the end of their service life in compliance with local regulations. EATON works with companies in charge of - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 7
you least expect it and power quality can be erratic. These power problems have the potential to corrupt critical data, destroy unsaved work sessions, • ABM® technology that uses advanced battery management to increase battery service life, optimize recharge time, and provide a warning before the - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 8
2. Presentation 2.1 Standard installations Tower installation D W H Rack installation D H W Description 9PX700RT 9PX1000RT 9PX1000GRT 9PX1500RT 9PX1500GRT 9PX2000RT 9PX2200GRT 9PX3000RT 9PX3000GRT 9PX3000GLRT 9PXEBM36RT 9PXEBM48RT 9PXEBM72RT Weights (lb/kg) 36.4 / 16.5 36.4 / 16.5 38.6 / 17.5 42 - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 9
ENGLISH 2.2 Rear panels 9PX 700RT / 9PX 1000RT / 9PX 1500RT 1 23 4 5 6 11 10 9 8 9PX 2000RT 1 238 4 7 5 6 9 11 10 7 9PX 1000GRT, 9PX 1500GRT, 9PX 2200GRT & 9PX 3000GRT 1 238 4 5 2. Presentation 1 Socket for connection to AC power source 2 Slot for optional communication card 3 - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 10
2. Presentation 9PX EBM 36V/48V 13 12 9PX EBM 72V 13 13 12 Connectors for battery modules (to the UPS or to the other battery modules) 13 Connectors for automatic recognition of battery modules 12 13 12 12 2.3 Accessories Part number 9PXEBM36RT2U 9PXEBM48RT2U 9PXEBM72RT2U 9RK - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 11
The UPS is on Battery mode. On Orange On Red The UPS is on Bypass mode. The UPS has an active alarm or fault. See troubleshooting on page 39 for additional information. 9PX 1-3 KVA US_EN Page 11 - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 12
Efficiency and load group information The following table describes the status information provided by the UPS Note: If other indicator appears, see troubleshooting on page 39 for additional information. Operation status Standby mode Cause The UPS is Off, waiting form startup command from user - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 13
Transfers the UPS on Bypass mode Commands the load segments Starts a manual battery test Tests dry contact relay outputs and relay card contacts. alarms, UPS fault, Event Log data and settings are in all supported languages. Format: [US] [International] [US] Modify LCD screen brightness - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 14
2. Presentation In/Out settings On/Off settings Submenu Available settings Default settings Output voltage [100V] [110V] [120V] [125V] [120V] [200V] [208V] [220V] [230V] [240V] [208V] Output frequency Mode: [Normal] [Converter] [Marine] [Normal] Frequency can be changed in Frequency [ - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 15
battery charge is reached. [ABM cycling] [Constant charge] Default settings [Every ABM cycle] [Every week] [0%] [3min] [0%] [ABM cycling] [Auto detection] [Manual EBM set.] [Manual battery set.] [Yes] [No] If set to Yes, the UPS automatically prevents battery from deep discharge by adapting end of - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 16
2. Presentation Com settings Submenu Output signals Available settings [Relay] [DB9-1] [DB9-7] [DB9-8] Sets events or fault that will actuate Output signal parameters through external contact connector or RS232 port Default settings [Relay]: [On bat] [Low bat] [Bat fault] [Bypass] [UPS OK] [ - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 17
passed and the batteries were never recharged, do not use the UPS. Contact your service representative. 3.2 Checking the accessory kit 9PX 700RT / 9PX 1000RT / 9PX 1500RT Manual CD-ROM 21 Software leaflet 22 Safety instructions 23 Quick start 24 Mounting kit for 19-inch enclosures 25 2 supports - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 18
17 RS232 communication cable 18 USB communication cable 19 3 cable locking systems 20 Manual CD-ROM 21 Software leaflet 22 Safety instructions 23 Quick start 24 Mounting kit for 19-inch enclosures 25 2 supports for tower position Elements supplied depending on the version or optional 26 NMC - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 19
source 17 RS232 communication cable 18 USB communication cable 19 Cable locking system 20 Manual CD-ROM 21 Software leaflet 22 Safety instructions 23 Quick start 24 Mounting kit for 19-inch enclosures 25 2 supports for tower position Elements supplied depending on the version or optional 26 NMC - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 20
1 Battery power cable with attached battery detection cable 2 Stabilizer bracket (4 screws included) 3 Rack kit for 19-inch enclosures (optional) 4 EBM Installation manual. 4 1 2 3 Discard the EBM user's guide if you are installing the EBM with a new UPS at the same time. Use the UPS user - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 21
ENGLISH 3.3 Connecting the internal battery Do not connect the UPS to utility until installation is completed. 3. Installation 2 1 3 4 5 To connect the UPS: 1. Remove the center cover of the front panel. 2. Push left cover toward to right direction. 3. Open the left side of the front panel. A - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 22
connector of the UPS and of the EBM(s). 9PXEBM48RT2U 9PXEBM72RT2U 3.5 Connecting other accessories If you ordered other UPS accessories, refer to to the UPS. user manuals to check the connection Page 22 9PX 1-3 KVA US_EN - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 23
ENGLISH 3. Installation 3.6 Tower installation If you ordered other UPS accessories, refer to specific user manuals to check the tower installation with the UPS. To install the cabinet: 1. Place the UPS on a flat, stable surface in its final location. 2. Always keep 6" - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 24
3. Installation 3.7 Rack installation • Rack mounting of UPS, EBM, and accessory modules. Follow steps 1 to 4 for module mounting on the rails. 1 1 2 3 3 4 4 The rails and necessary hardware are supplied by EATON. Page 24 9PX 1-3 KVA US_EN - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 25
ENGLISH 3. Installation 3.8 UPS connection without HotSwap MBP module Check that the indications on the name plate located on the back of the UPS correspond to the AC-power source and the true electrical consumption of the total load. 1. 9PX 2000RT / 3000RT : connect the UPS input socket 1 to - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 26
3. Installation 3.9 Connection with a HotSwap MBP module (optional accessory) The HotSwap MBP module makes it possible to service or even replace the UPS without affecting the connected loads. 9PX 2000RT 1 238 4 5 6 9 11 10 7 28 MBP-120 29 33 34 35 36 LOAD 15 - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 27
ENGLISH 3. Installation 9PX 2200GRT & 9PX 3000GRT 5 1 MBP 6 7 28 29 30 31 32 33 34 35 36 15 LOAD HotSwap MBP module operation 1. Connect the input 36 on the HotSwap MBP module to the AC-power source. 2. Connect the UPS input cable 1 to the "UPS Input socket" 35 on the HotSwap MBP - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 28
4. Communication 4.1 Communication ports Connection of RS232 or USB communication port The RS232 and USB communication ports cannot operate simultaneously. 1. Connect the RS232 17 or USB 18 18 communication cable to the serial or USB port on the com- puter equipment. 2. Connect the other - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 29
ENGLISH 4. Communication 4.2 UPS remote control functions Programmable Signal Inputs The 9PX incorporates 3 programmable signal inputs: one Remote Power Off (RPO) input terminal, one Remote On/Off (ROO) input terminal, one RS-232 input (pin-4). Signal inputs can be configured (see Settings > Com - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 30
4. Communication • Remote On/Off (ROO) Remote On/Off allows remote action of button to switch On/Off the UPS. When contact changes from open to closed, the UPS is switched-on (or stays On). When contact changes from closed to open, the UPS is switched-off (or stays Off). On/Off control via button - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 31
ENGLISH 4. Communication Connectivity Cards Connectivity cards allow the UPS to communicate in a variety of networking environments and with different types of devices. The 9PX models have one available communication bay for the following connectivity cards: • Network-MS card - has SNMP and HTTP - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 32
changes status to "UPS starting...". 7. Check the UPS front panel display for active alarms or notices. Resolve any active alarms before continuing. See "Troubleshooting" on page 39. If the indicator is on, do not proceed until all alarms are clear. Check the UPS status from the front panel to - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 33
ENGLISH 5. Operation Low-battery warning • The indicator illuminates solid. • The audio alarm beeps every three seconds. The remaining battery power is low. Shut down all applications on the connected equipment because automatic UPS shutdown is imminent. End of battery backup time • LCD displays " - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 34
(0 % by default). This threshold can be modified. External battery setting The number of Extended Battery Module is automatically detected, or can be set manually in number of EBM or in Ah. Deep discharge protection This setting is recommended to avoid damaging the battery. Warranty is void if deep - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 35
date on the shipping carton label. If the date has passed and the batteries were never recharged, do not use them. Contact your service representative. 6.3 When to replace batteries Eaton UPS batteries have an expected life span of 3-5 years. After 4 years of operation, the UPS will provide - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 36
Wear rubber gloves and boots. • When replacing batteries, replace with the same type and number of batteries or battery packs. Contact your service representative to order new batteries. • Proper disposal of batteries is required. Refer to your local codes for disposal requirements. • Never dispose - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 37
out the plastic handle of the battery pack, and slide the pack out slowly on to a flat and stable sur- face. Use two hands to support the battery pack. See "Recycling the used equipment" on page 38 for proper disposal. 7. Verify that the replacement batteries have the same rating as the - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 38
6. UPS maintenance 6.5 Replacing the UPS equipped with a HotSwap MBP 1 2 3 8 4 5 6 The HotSwap MBP module makes it possible to service or even replace the UPS without affecting the connected loads. Maintenance 1. Set switch 33 to Bypass position. 9 11 10 7 The red LED on the HotSwap - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 39
7. Troubleshooting The Eaton 9PX are designed for durable, automatic operation and also alert you whenever potential operating problems may occur hours to charge the batteries. If the condition persists, contact your service representative. Equipment is powered but not protected by the UPS. Check - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 40
7. Troubleshooting UPS overtemperature LED is On. 1 beep every 3 seconds. The UPS does not start. overriding the previous alarm silencing. 7.3 Service and support If you have any questions or problems with the UPS, call your Local Distributor or your local service representative and ask for a UPS - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 41
ENGLISH 8.1 Model specifications Input Filter Bypass AC/DC Boost DC/AC Inverter DC/DC Outpout Filter 8. Specifications Charger Battery Table 1. Power Module model list Model 9PX700RT 9PX1000RT Power ratings 700VA / 630W 1000VA / 900W 9PX1000GRT 1000VA / 900W 9PX1500RT 1500VA / 1350W - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 42
8. Specifications Table 4. Electrical input Nominal frequency Frequency range Bypass voltage range Noise filtering Model 9PX700RT 9PX1000RT 9PX1500RT 9PX2000RT 9PX3000RT 9PX1000GRT 9PX1500GRT 9PX2200GRT 9PX3000GRT 9PX3000GLRT 50/60Hz auto-sensing 40-70Hz before transfer to battery -20% / +15% of - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 43
ENGLISH 8. Specifications Table 6. Electrical output All models Voltage regulation Efficiency Frequency regulation Nominal output Frequency Output overload Output overload (Bypass mode) Voltage waveform Harmonic distortion Transfer time Power factor Load crest ratio Normal mode Efficiency mode - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 44
, 7Ah 9PXEBM48RT: 48Vdc - 2 x 4 x 12V, 9Ah 9PXEBM72RT: 72Vdc - 2 x 6 x 12V, 9Ah Sealed, maintenance-free, valve-regulated, lead-acid, with minimum 3-year float service life at 25°C (77°F). Lifetime is reduced above 25°C (77°F). Advanced monitoring for earlier failure detection and warning 350 mm - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 45
bypass Rotary switch controlled by the user, used to connect the loads directly to the AC source. Transfer of the load to the manual bypass enables UPS maintenance without interrupting the supply of power to the connected loads. Normal (double conversion) mode The normal UPS operating mode in - Tripp Lite 9PX11KTF11M | Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 46
Page 46 9PX 1-3 KVA US_EN
ENGLISH
9PX 700 RT
9PX 1000 RT
9PX 1000GRT
9PX 1500 RT
9PX 1500GRT
9PX 2000 RT
9PX 2200 GRT
9PX 3000 RT
9PX 3000 GRT
9PX 3000 GLRT
9PX EBM 36V RT
9PX EBM 48V RT
9PX EBM 72V RT
Installation
and user manual
Copyright © 2016
EATON
All rights reserved.
9PX 1-3 KVA US_EN