FAQS Symptom Possible Cause What To Do UPS will not turn on On/Off/Test button not pushed Press the On button momentarily (one beep to start UPS) UPS operates in battery mode only, even though there is normal AC present Input AC circuit breaker is tripped Reset circuit breaker by pressing the plunger back in. If the AC circuit breaker trips after UPS starts up, reduce the load on the UPS. The UPS emits a sustained tone UPS has detected an internal Call for service fault The Site Wiring Fault LED is illuminated Incorrect service wiring Have a qualified electrician correct the service wiring The Battery On LED is illuminated, but there is no output The UPS is being controlled via its computer port. Disconnect the computer cable from the UPS and press the On button momentarily. If UPS works normally, software has control of the UPS. UPS does not provide expected backup time with internal batteries or with a battery pack The batteries may be weak or at the end of useful service life. The battery pack's circuit breaker may be tripped. Charge the batteries for 8 hours and retest. If the backup time is still less than expected, the batteries may need to be replaced, even though the Weak/Bad Battery LED is not illuminated. Reset the battery pack's circuit breaker. Replace Battery LED is illuminated Weak or bad batteries/bad battery connection Check battery connection/ replace batteries. Follow battery replacement procedures in section 6. UPS occasionally emits a beep Normal operation The UPS is performing its intended function. Overload LED is illuminated and The load has exceeded the UPS' Check the specifications (see a constant alarm sounds capacity section 8). Remove part of the load. The Battery On LED is blinking The UPS is in either the Buck The UPS is performing its and the audible alarm is silent mode or the Boost mode intended function. 24 MAINTENANCE Battery Replacement The OmniGuard Rackmount series has easy-to-replace hot-swappable batteries. Please read the following warning statements before attempting to service the battery(s). NOTE: If there is a power interruption while replacing the hotswappable batteries, with the UPS on, the load will not be backed up. WARNING: This Uninterruptible Power Source contains potentially hazardous voltages. Do not attempt to disassemble the unit beyond battery replacement procedures below. Except for the battery, this UPS contains no user-serviceable parts. Repairs should be performed by service personnel only CAUTION: Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes and may be toxic. CAUTION: Although battery system voltages are only 24VDC and 48VDC, the battery system can still present a risk of electrical shock. The current capability of a battery is sufficient to burn wire or tools very rapidly, producing molten metal. Observe these precautions when replacing the batteries: 1. Remove watches, rings, or other metal objects. 2. Use hand tools with insulated handles. 3. Do not lay tools or other metal parts on top of batteries. CAUTION: Replace batteries with the same number and type as originally installed in the UPS. These batteries have pressureoperated vents. Series Model # Battery Model # F6C110-RKM-2U 12V 7.2Ah F6C150-RKM-2U 12V 4.5Ah F6C230-RKM-2U 12V 9Ah F6C320-RKM-3U 12V 12Ah 25

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17

MAINTENANCE
25
FAQS
24
Battery Replacement
The OmniGuard Rackmount series has easy-to-replace hot-swappable batteries.
Please read the following warning statements before attempting to service the
battery(s). NOTE: If there is a power interruption while replacing the hot-
swappable batteries, with the UPS on, the load will not be backed up.
Symptom
UPS will not turn on
UPS operates in battery mode
only, even though there is
normal AC present
The UPS emits a sustained tone
The Site Wiring Fault LED is
illuminated
The Battery On LED is
illuminated, but there
is no output
UPS does not provide expected
backup time with internal
batteries or with a battery pack
Replace Battery LED is
illuminated
UPS occasionally emits a beep
Overload LED is illuminated and
a constant alarm sounds
The Battery On LED is blinking
and the audible alarm is silent
Possible Cause
On/Off/Test button not pushed
Input AC circuit breaker is
tripped
UPS has detected an internal
fault
Incorrect service wiring
The UPS is being controlled via
its computer port.
The batteries may be weak or
at the end of useful service life.
The battery pack’s circuit
breaker may be tripped.
Weak or bad batteries/bad
battery connection
Normal operation
The load has exceeded the UPS’
capacity
The UPS is in either the Buck
mode or the Boost mode
What To Do
Press the On button
momentarily (one beep to
start UPS)
Reset circuit breaker by
pressing the plunger back in.
If the AC circuit breaker trips
after UPS starts up, reduce the
load on the UPS.
Call for service
Have a qualified electrician
correct the service wiring
Disconnect the computer cable
from the UPS and press the On
button momentarily. If UPS
works normally, software has
control of the UPS.
Charge the batteries for 8 hours
and retest. If the backup time
is still less than expected, the
batteries may need to be
replaced, even though the
Weak/Bad Battery LED is not
illuminated. Reset the battery
pack’s circuit breaker.
Check battery connection/
replace batteries. Follow battery
replacement procedures in
section 6.
The UPS is performing its
intended function.
Check the specifications (see
section 8). Remove part of the
load.
The UPS is performing its
intended function.
WARNING:
This Uninterruptible Power Source contains
potentially hazardous voltages. Do not attempt to disassemble
the unit beyond battery replacement procedures below. Except
for the battery, this UPS contains no user-serviceable parts.
Repairs should be performed by service personnel only
Series Model #
Battery Model #
F6C110-RKM-2U
12V 7.2Ah
F6C150-RKM-2U
12V 4.5Ah
F6C230-RKM-2U
12V 9Ah
F6C320-RKM-3U
12V 12Ah
CAUTION:
Do not open or mutilate batteries. Released
electrolyte is harmful to the skin and eyes and may be toxic.
CAUTION:
Although battery system voltages are only 24VDC
and 48VDC, the battery system can still present a risk of
electrical shock. The current capability of a battery is sufficient
to burn wire or tools very rapidly, producing molten metal.
Observe these precautions when replacing the batteries:
1.
Remove watches, rings, or other metal objects.
2.
Use hand tools with insulated handles.
3.
Do not lay tools or other metal parts on top of batteries.
CAUTION:
Replace batteries with the same number and type as
originally installed in the UPS. These batteries have pressure-
operated vents.