length/ slack has been adjusted, attach strain relief per instructions included with strain relief. Tip: The knockout panel below the terminal block can be removed from the range to install the strain relief: Remove knockout panel from range, install strain relief in panel and reattach. DO NOT remove entire range back panel. Figure 8: Strain Relief Knockout Warning: Risk of Electric Shock or Fire. Frame grounded to neutral through a ground strap. Grounding through the neutral conductor is prohibited for new branch-circuit installations (1996 NEC), mobile homes, and recreational vehicles, or in an area where local codes prohibit grounding through the neutral conductor. For installations where grounding through the neutral conductor is prohibited, (a) disconnect the link from the neutral, (b) use grounding terminal or lead to ground unit, (c) connect neutral terminal to lead branch circuit neutral in usual manner (when the appliance is to be connected by means of a cord kit, use 4conductor cord for this purpose). Use only cord kits rated 125/250 volts (minimum), 40 or 50 amperes (depending on local code) and labeled "For Use with Ranges". Strain relief provided with cord must be installed per instructions Figure 9: Grounding Requirements Warning: To prevent electrical shock, the grounding prong on the range cord should not be cut or removed under any circumstances. It must be plugged into a matching grounding type receptacle and connected to a correctly polarized 240- Volt circuit. If there is any doubt as to whether the wall receptacle is properly grounded, have it checked by a qualified electrician. English 9

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56

English 9
length/ slack has been adjusted, attach strain relief per instructions included with
strain relief.
Warning:
To prevent electrical shock, the grounding prong on the range
cord should not be cut or removed under any circumstances. It must be plugged
into a matching grounding type receptacle and connected to a correctly polarized
240- Volt circuit. If there is any doubt as to whether the wall receptacle is properly
grounded, have it checked by a qualified electrician.
Figure 8: Strain Relief Knockout
Figure 9: Grounding Requirements
Tip: The knockout panel below the terminal block can be removed from
the range to install the strain relief: Remove knockout panel from range,
install strain relief in panel and reattach. DO NOT remove entire range
back panel.
Warning:
Risk of Electric Shock or Fire. Frame grounded to neutral
through a ground strap. Grounding through the neutral conductor is prohibited
for new branch-circuit installations (1996 NEC), mobile homes, and recreational
vehicles, or in an area where local codes prohibit grounding through the neutral
conductor.
For installations where grounding through the neutral conductor is prohibited,
(a) disconnect the link from the neutral, (b) use grounding terminal or lead to
ground unit, (c) connect neutral terminal to lead branch circuit neutral in usual
manner (when the appliance is to be connected by means of a cord kit, use 4-
conductor cord for this purpose).
Use only cord kits rated 125/250 volts (minimum), 40 or 50 amperes (depend-
ing on local code) and labeled “For Use with Ranges”. Strain relief provided
with cord must be installed per instructions