Bosch HES7132U Installation Instructions - Page 7

Warning - ratings

Page 7 highlights

Installation Installation Tips 1) Install Ventilation 2) Prepare Walls and Floor 3) Prepare Range 4) Install Strain Relief For installations other than those in Canada, in stall the strain relief and connect the range cord (or wire conductors) as described in the following steps. Table 1: Electrical Specifications Check data plate for kW rating. Reference kW rating in table to determine amperage requirements. kW Rating AMPS Required At 120/240 Volts: 12.3 12.6 13.5 At 120/208 Volts: 9.2 9.5 10.2 US Models: Canadian Models: 40 or 50* 40 or 50* 50 50 * Varies by location. Refer to local electric code. • Tape warming drawer or storage drawer shut to keep it from opening while installing the range. • During installation, place a portion of the box or a piece of cloth under the range to protect floors. • To make range lighter and easier to handle, remove door (see instructions in Use and Care manual). We strongly recommend the installation of a ventilation hood above this range. For most kitchens a certified hood rating of not less than 300 CFM is recommended. The range hood must be installed according to instructions furnished with the hood. Seal any holes in the walls or floor. Remove any obstructions (extra electrical or gas connections, etc.) so that range will rest against wall properly. Place range in front of cabinets where it is to be installed. Remove any packaging. WARNING: The strain relief provided with your range cord must be properly installed. Place strain relief in knockout below terminal block (See Figure 4). Feed range cord through hole and strain relief up to terminal block. Allow for slack in the cord between the strain relief and terminal block. Once cord length/ slack has been adjusted, attach strain relief per instructions included with strain relief. Tip: The knockout panel (below the terminal block) can be removed from the range to install the strain relief: Remove panel from range, install strain relief in panel and reattach. DO NOT remove entire range back panel. English 5

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48

English 5
For installations other than those in Canada, in stall the strain relief and connect
the range cord (or wire conductors) as described in the following steps.
* Varies by location. Refer to local electric code.
Installation
Installation Tips
Tape warming drawer or storage drawer shut to keep it from opening while
installing the range.
During installation, place a portion of the box or a piece of cloth under the
range to protect floors.
To make range lighter and easier to handle, remove door (see instructions in
Use and Care manual).
1) Install Ventilation
We strongly recommend the installation of a ventilation hood above this range.
For most kitchens a certified hood rating of not less than 300 CFM is recom-
mended. The range hood must be installed according to instructions furnished
with the hood.
2) Prepare Walls and Floor
Seal any holes in the walls or floor. Remove any obstructions (extra electrical or
gas connections, etc.) so that range will rest against wall properly.
3) Prepare Range
Place range in front of cabinets where it is to be installed. Remove any packaging.
4) Install Strain Relief
WARNING:
The strain relief provided with your range cord must be
properly installed.
Place strain relief in knockout below terminal block (See Figure 4). Feed range
cord through hole and strain relief up to terminal block. Allow for slack in the cord
between the strain relief and terminal block. Once cord length/ slack has been
adjusted, attach strain relief per instructions included with strain relief.
Tip:
The knockout panel (below the terminal block) can be removed from the
range to install the strain relief: Remove panel from range, install strain relief in
panel and reattach. DO NOT remove entire range back panel.
Table 1:
Electrical Specifications
Check data plate for kW rating. Reference kW rating in table to determine amper-
age requirements.
kW Rating
AMPS Required
At 120/240 Volts:
At 120/208 Volts:
US Models:
Canadian Models:
12.3
9.2
40 or 50*
12.6
9.5
40 or 50*
50
13.5
10.2
50