Dell PowerEdge 6850 Installation and Troubleshooting Guide (.htm) - Page 13
Marking the Rack - rails
View all Dell PowerEdge 6850 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 13 highlights
Marking the Rack You must allow 4 U (7 inches) of vertical space for each system you install in the rack (see Figure 1-3). NOTE: Your rack may already be marked and not require this procedure. Figure 1-3. One Rack Unit 1 U (44 mm or 1.75 inches) 12.7 mm (0.5 inch) 15.9 mm (0.625 inch) 15.9 mm (0.625 inch) 12.7 mm (0.5 inch) CAUTION: If you are installing more than one system, install the slide assemblies so that the first system is installed in the lowest available position in the rack. To mark the rack, perform the following steps: 1 Place a mark on the rack's front vertical rails where you want to locate the bottom of the system you are installing in the rack cabinet. The bottom of each 1-U space is at the middle of the narrowest metal area between holes (marked with a horizontal line on some rack cabinets- see Figure 1-4). Dell™ Rack Installation Guide 11