Dell PowerEdge C6420 EMC Technical Specifications 1 - Page 16

Expanded operating temperature specifications, Operating temperature derating specifications

Page 16 highlights

TDP Watts 105 W 85 W 70 W 3.5-inch chassis 12x HDDs Not supported Not supported Not supported 8x HDDs Not supported Not supported Not supported 4x HDDs Not supported Not supported Not supported 24x HDDs 25 30 >35 2.5-inch chassis 16x HDDs 25 8x HDDs 25 30 30 >35 >35 4x HDDs 25 30 >35 No-BP Chassis N/A 30 >35 >35 Expanded operating temperature specifications Table 14. Expanded operating temperature Expanded operating temperature Continuous operation ≤ 1% of annual operating hours Specifications 5°C-40°C at 5% to 85% RH with maximum 29°C dew point. NOTE: Outside the standard operating temperature (10°C-35°C), the system can operate continuously in temperatures as low as 5°C and as high as 40°C. For temperatures between 35°C-40°C, derate maximum allowable temperature by 1°C per 175 m above 950 m (1°F per 319 ft). -5°C-45°C at 5% to 90% RH with maximum 29°C dew point. NOTE: Outside the standard operating temperature (10°C-35°C), the system can operate down to - 5°C-45°C for a maximum of 1% of its annual operating hours. For temperatures between 40°C-45°C, derate maximum allowable temperature by 1°C per 125 m above 950 m (1°F per 228 ft). NOTE: When operating in the expanded temperature range, system performance may be impacted. NOTE: When operating in the expanded temperature range, ambient temperature warnings may be reported in the System Event Log. Operating temperature derating specifications Table 15. Operating temperature Operating temperature derating < 35°C (95°F) Specifications Maximum temperature is reduced by 1°C/300 m (1°F/547 ft) above 950 meters (3,117 ft) 35°C-40°C (95°F-104°F) Maximum temperature is reduced by 1°C/175 m (1°F/319 ft) above 950 meters (3,117 ft) > 45°C (113°F) Maximum temperature is reduced by 1°C/125 m (1°F/228 ft) above 950 meters (3,117 ft) 16 Technical specifications

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23

TDP Watts
3.5-inch chassis
2.5-inch chassis
No-BP
Chassis
12x HDDs
8x HDDs
4x HDDs
24x HDDs
16x HDDs
8x HDDs
4x HDDs
N/A
105 W
Not
supported
Not
supported
Not
supported
25
25
25
25
30
85 W
Not
supported
Not
supported
Not
supported
30
30
30
30
>35
70 W
Not
supported
Not
supported
Not
supported
>35
>35
>35
>35
>35
Expanded operating temperature specifications
Table 14. Expanded operating temperature
Expanded operating temperature
Specifications
Continuous operation
5°C–40°C at 5% to 85% RH with maximum 29°C dew point.
NOTE:
Outside the standard operating temperature
(10°C–35°C), the system can operate continuously in
temperatures as low as 5°C and as high as 40°C.
For temperatures between 35°C-40°C, derate maximum allowable
temperature by 1°C per 175 m above 950 m (1°F per 319 ft).
≤ 1% of annual operating hours
–5°C–45°C at 5% to 90% RH with maximum 29°C dew point.
NOTE:
Outside the standard operating temperature
(10°C–35°C), the system can operate down to –
5°C-45°C for a maximum of 1% of its annual operating
hours.
For temperatures between 40°C-45°C, derate maximum allowable
temperature by 1°C per 125 m above 950 m (1°F per 228 ft).
NOTE:
When operating in the expanded temperature range, system performance may be impacted.
NOTE:
When operating in the expanded temperature range, ambient temperature warnings may be reported in the
System Event Log.
Operating temperature derating specifications
Table 15. Operating temperature
Operating temperature derating
Specifications
< 35°C (95°F)
Maximum temperature is reduced by 1°C/300 m (1°F/547 ft)
above 950 meters (3,117 ft)
35°C–40°C (95°F–104°F)
Maximum temperature is reduced by 1°C/175 m (1°F/319 ft)
above 950 meters (3,117 ft)
> 45°C (113°F)
Maximum temperature is reduced by 1°C/125 m (1°F/228 ft)
above 950 meters (3,117 ft)
16
Technical specifications