Dell PowerEdge C6420 EMC Technical Specifications 1 - Page 17

Relative humidity specifications, Temperature specifications

Page 17 highlights

Relative humidity specifications Table 16. Relative humidity specifications Relative humidity Storage Operating Specifications 5% to 95% RH with 33°C (91°F) maximum dew point. Atmosphere must be non-condensing at all times. 10% to 80% relative humidity with 29°C (84.2°F) maximum dew point Temperature specifications Table 17. Temperature specifications Temperature Storage Continuous operation (for altitude less than 950 m or 3117 ft) Fresh air Maximum temperature gradient (operating and storage) Specifications -40°C-65°C (-40°F-149°F) 10°C-35°C (50°F-95°F) with no direct sunlight on the equipment. For information about fresh air, see Expanded Operating Temperature section. 20°C/h (68°F/h) NOTE: Some configurations require a lower ambient temperature for more information, see the Standard operating temperature specifications. Particulate and gaseous contamination specifications Table 18. Particulate contamination specifications Particulate contamination Specifications Air filtration Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a 95% upper confidence limit. NOTE: This condition applies only to data center environments. Air filtration requirements do not apply to IT equipment designed to be used outside a data center, in environments such as an office or factory floor. NOTE: Air entering the data center must have MERV11 or MERV13 filtration. Conductive dust Air must be free of conductive dust, zinc whiskers, or other conductive particles. NOTE: This condition applies to data center and non-data center environments. Corrosive dust Air must be free of corrosive dust. Residual dust present in the air must have a deliquescent point less than 60% relative humidity. NOTE: This condition applies to data center and non-data center environments. Technical specifications 17

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23

Relative humidity specifications
Table 16. Relative humidity specifications
Relative humidity
Specifications
Storage
5% to 95% RH with 33°C (91°F) maximum dew point.
Atmosphere must be non-condensing at all times.
Operating
10% to 80% relative humidity with 29°C (84.2°F) maximum dew
point
Temperature specifications
Table 17. Temperature specifications
Temperature
Specifications
Storage
–40°C–65°C (–40°F-149°F)
Continuous operation (for altitude less than 950 m or 3117 ft)
10°C–35°C (50°F-95°F) with no direct sunlight on the
equipment.
Fresh air
For information about fresh air, see Expanded Operating
Temperature section.
Maximum temperature gradient (operating and storage)
20°C/h (68°F/h)
NOTE:
Some configurations require a lower ambient temperature for more information, see the
Standard operating
temperature specifications
.
Particulate and gaseous contamination specifications
Table 18. Particulate contamination specifications
Particulate contamination
Specifications
Air filtration
Data center air filtration as defined by ISO
Class 8 per ISO 14644-1 with a 95% upper
confidence limit.
NOTE:
This condition applies only to data center environments. Air filtration requirements do not apply to IT equipment
designed to be used outside a data center, in environments such as an office or factory floor.
NOTE:
Air entering the data center must have MERV11 or MERV13 filtration.
Conductive dust
Air must be free of conductive dust, zinc
whiskers, or other conductive particles.
NOTE:
This condition applies to data center and non-data center environments.
Corrosive dust
Air must be free of corrosive dust.
Residual dust present in the air must have a deliquescent point less than 60% relative humidity.
NOTE:
This condition applies to data center and non-data center environments.
Technical specifications