Table 11. Maximum altitude specifications (continued) Maximum altitude Specifications Storage 12,000 m (39,370 ft) Table 12. Operating temperature de-rating specifications Operating temperature de-rating Specifications Up to 35°C (95°F) Maximum temperature is reduced by 1°C/300 m (1°F/547 ft) above 950 m (3,117 ft). 35°C to 40°C (95°F to 104°F) Maximum temperature is reduced by 1°C/175 m (1°F/319 ft) above 950 m (3,117 ft). 40°C to 45°C (104°F to 113°F) Maximum temperature is reduced by 1°C/125 m (1°F/228 ft) above 950 m (3,117 ft). Standard operating temperature Table 13. Standard operating temperature specifications Standard operating temperature Specifications Continuous operation (for altitude less than 950 m or 3117 10°C to 35°C (50°F to 95°F) with no direct sunlight on the equipment. ft) Expanded operating temperature Table 14. Expanded operating temperature specifications Expanded operating temperature Specifications Continuous operation 5°C-40°C at 5% to 85% RH with 29°C dew point. NOTE: Outside the standard operating temperature (10°C- 35°C), the system can operate continuously in temperatures as low as 5°C and as high as 40°C. For temperatures between 35°C-40°C, de-rate maximum allowable temperature by 1°C per 175 m above 950 m (1°F per 319 ft). ≤ 1% of annual operating hours -5°C-45°C at 5% to 90% RH with 29°C dew point. NOTE: Outside the standard operating temperature (10°C- 35°C), the system can operate down to -5°C or up to 45°C for a maximum of 1% of its annual operating hours. For temperatures between 40°C and 45°C, de-rate maximum allowable temperature by 1°C per 125 m above 950 m (1°F per 228 ft). NOTE: When operating in the expanded temperature range, system performance may be impacted. NOTE: When operating in the expanded temperature range, ambient temperature warnings may be reported on the LCD panel and in the System Event Log. Expanded operating temperature restrictions • Do not perform a cold startup below 5°C. • The operating temperature specified is for a maximum altitude of 3050 m (10,000 ft). • 150 W/8 C, 165 W/12 C and higher wattage processor(TDP>165 W) are not supported. • Redundant power supply unit is required. • Non-Dell qualified peripheral cards and/or peripheral cards greater than 25 W are not supported. • NVDIMM-Ns are not supported. 12 Technical specifications

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20

Table 11. Maximum altitude specifications (continued)
Maximum altitude
Specifications
Storage
12,000 m (39,370 ft)
Table 12. Operating temperature de-rating specifications
Operating temperature de-rating
Specifications
Up to 35°C (95°F)
Maximum temperature is reduced by 1°C/300 m (1°F/547 ft) above 950 m
(3,117 ft).
35°C to 40°C (95°F to 104°F)
Maximum temperature is reduced by 1°C/175 m (1°F/319 ft) above 950 m
(3,117 ft).
40°C to 45°C (104°F to 113°F)
Maximum temperature is reduced by 1°C/125 m (1°F/228 ft) above 950 m
(3,117 ft).
Standard operating temperature
Table 13. Standard operating temperature specifications
Standard operating temperature
Specifications
Continuous operation (for altitude less than 950 m or 3117
ft)
10°C to 35°C (50°F to 95°F) with no direct sunlight on the equipment.
Expanded operating temperature
Table 14. Expanded operating temperature specifications
Expanded operating temperature
Specifications
Continuous operation
5°C–40°C at 5% to 85% RH with 29°C dew point.
NOTE:
Outside the standard operating temperature (10°C–
35°C), the system can operate continuously in temperatures as
low as 5°C and as high as 40°C.
For temperatures between 35°C–40°C, de-rate maximum allowable
temperature by 1°C per 175 m above 950 m (1°F per 319 ft).
≤ 1% of annual operating hours
–5°C–45°C at 5% to 90% RH with 29°C dew point.
NOTE:
Outside the standard operating temperature (10°C–
35°C), the system can operate down to –5°C or up to 45°C for a
maximum of 1% of its annual operating hours.
For temperatures between 40°C and 45°C, de-rate maximum allowable
temperature by 1°C per 125 m above 950 m (1°F per 228 ft).
NOTE:
When operating in the expanded temperature range, system performance may be impacted.
NOTE:
When operating in the expanded temperature range, ambient temperature warnings may be reported on the LCD
panel and in the System Event Log.
Expanded operating temperature restrictions
Do not perform a cold startup below 5°C.
The operating temperature specified is for a maximum altitude of 3050 m (10,000 ft).
150 W/8 C, 165 W/12 C and higher wattage processor(TDP>165 W) are not supported.
Redundant power supply unit is required.
Non-Dell qualified peripheral cards and/or peripheral cards greater than 25 W are not supported.
NVDIMM-Ns are not supported.
12
Technical specifications