Dell PowerEdge T440 EMC Technical Specifications 1 - Page 13

Particulate and gaseous contamination specifications

Page 13 highlights

Storage configuration Processor number Intel Xeon Bronze 3106 TDP (W) 85 Intel Xeon Bronze 85 3104 Intel Xeon Silver 4112 85 Core count 8 6 4 4x 3.5-inch cable drive Yes 8x 3.5-inch drive 16x 2.5-inch drive Ambient support = 35°C Yes Yes Yes Yes Yes Yes Yes Yes Particulate and gaseous contamination specifications The following table defines the limitations that help avoid any equipment damage or failure from particulate and gaseous contamination. If the levels of particulate or gaseous pollution exceed the specified limitations and result in equipment damage or failure, you may need to rectify the environmental conditions. Remediation of environmental conditions is the responsibility of the customer. Table 16. Particulate contamination specifications Particulate contamination Specifications Air filtration Data center air filtration defines, ISO Class 8 per ISO 14644-1 with a 95% upper confidence limit. NOTE: The ISO Class 8 condition applies to data center environments only. This air filtration requirement does not apply to IT equipment designed to be used outside a data center, in environments such as an office or factory floor. NOTE: Air entering the data center must have MERV11 or MERV13 filtration. Conductive dust Air must be free of conductive dust, zinc whiskers, or other conductive particles. NOTE: This condition applies to data center and nondata center environments. Corrosive dust • Air must be free of corrosive dust. • Residual dust present in the air must have a deliquescent point less than 60% relative humidity. NOTE: This condition applies to data center and nondata center environments. Table 17. Gaseous contamination specifications Gaseous contamination Copper coupon corrosion rate Silver coupon corrosion rate Specifications

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18

Storage
configuration
4x 3.5-inch cable
drive
8x 3.5-inch drive
16x 2.5-inch drive
Processor number
TDP (W)
Core count
Ambient support = 35°C
Intel Xeon Bronze
3106
85
8
Yes
Yes
Yes
Intel Xeon Bronze
3104
85
6
Yes
Yes
Yes
Intel Xeon Silver 4112
85
4
Yes
Yes
Yes
Particulate and gaseous contamination
specifications
The following table
defines
the limitations that help avoid any equipment damage or failure from particulate and gaseous contamination. If
the levels of particulate or gaseous pollution exceed the
specified
limitations and result in equipment damage or failure, you may need to
rectify the environmental conditions. Remediation of environmental conditions is the responsibility of the customer.
Table 16. Particulate contamination
specifications
Particulate
contamination
Specifications
Air
filtration
Data center air
filtration
defines,
ISO Class 8 per ISO 14644-1 with a 95% upper
confidence
limit.
NOTE:
The ISO Class 8 condition applies to data center environments only. This air
filtration
requirement does not apply to IT equipment designed to be used outside a data center, in
environments such as an
office
or factory
floor.
NOTE:
Air entering the data center must have MERV11 or MERV13
filtration.
Conductive dust
Air must be free of conductive dust, zinc whiskers, or other conductive particles.
NOTE:
This condition applies to data center and nondata center environments.
Corrosive dust
Air must be free of corrosive dust.
Residual dust present in the air must have a deliquescent point less than 60% relative humidity.
NOTE:
This condition applies to data center and nondata center environments.
Table 17. Gaseous contamination
specifications
Gaseous contamination
Specifications
Copper coupon corrosion rate
<300 Å/month per Class G1
defines,
ANSI/ISA71.04-2013.
Silver coupon corrosion rate
<200 Å/month
defines
, ANSI/ISA71.04-2013.
NOTE:
Maximum corrosive contaminant levels measured at ≤50% relative humidity.
Technical
specifications
13