Fluke 1750 Fluke 1750 Operators Manual - Page 44
Meter Screen, Phasor Screen, Meter, Phasor, Menu\1750 Setup\Phase Swap
View all Fluke 1750 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 44 highlights
1750 Operators Manual Meter Screen The Meter screen shows numeric readings for all selected phases. Azd122.bmp Phasor Screen The Phasor screen shows voltage (long arrows with solid arrowheads), current amplitudes, and phase angles. This screen is used to verify proper test lead and current probe connections. You can use the V and A arrows on the upper right of the screen to change the scaling of voltage and current on the PHASOR diagram. You can easily correct an erroneous Recorder connection by going directly to Menu\1750 Setup\Phase Swap ( ) and using the Recorder to internally invert a CT, swap a voltage or CT phase, or modify a scaling parameter, then return to the screen to verify that the correction has been made. There is no need to touch the cables. See "Phase Swap" later in the manual for additional information. Azd123.bmp 36