GE DCVH485EKMS Use and Care Manual - Page 13

Installation Instructions

Page 13 highlights

Installation Instructions REQUIREMENTS FOR ALCOVE OR CLOSET INSTALLATION • Your dryer is approved for installation in an alcove or closet, as stated on a label on the dryer back. • The dryer MUST be vented to the outdoors. See the EXHAUSTING THE DRYER section. • Minimum clearance between dryer cabinet and adjacent walls or other surfaces is: 0″ either side 3″ front and rear • Minimum vertical space from floor to overhead shelves, cabinets, ceilings, etc., is 52″. • Closet doors must be louvered or otherwise ventilated and have at least 60 square inches of open area equally distributed. If the closet contains both a washer and a dryer, doors must contain a minimum of 120 square inches of open area equally distributed. NOTE: WHEN THE EXHAUST DUCT IS LOCATED AT THE REAR OF THE DRYER, MINIMUM CLEARANCE FROM THE WALL IS 5.5 INCHES. UNDERCOUNTER INSTALLATION If an undercounter installation is desired: • No special dryer installation kit is required. • If the dryer is installed alone, a minimum of 60 square inches of open area is required. If a washer and dryer are installed together, a minimum of 120 square inches of open area is required. Dryer installed alone Countertop and side cabinets 60 square inches min. open area 120 square inches min. open area Washer and Dryer installed together Countertop and side cabinets Wire frame spacer 5.5″ (140 mm) BATHROOM OR BEDROOM INSTALLATION • The dryer MUST be vented to the outdoors. See EXHAUSTING THE DRYER. • The installation must conform with local codes or, in the absence of local codes, with the NATIONAL ELECTRICAL CODE, ANSI/NFPA NO. 70 (for electric dryers) or NATIONAL FUEL GAS CODE, ANSI Z223 (for gas dryers). 13 MOBILE OR MANUFACTURED HOME INSTALLATION • The installation must conform to the MANUFACTURED HOME CONSTRUCTION & SAFETY STANDARD, TITLE 24, PART 32-80 or, when such standard is not applicable, with AMERICAN NATIONAL STANDARD FOR MOBILE HOME, NO. 501B. • The dryer MUST be vented to the outdoors with the termination securely fastened to the mobile home structure. (See EXHAUSTING THE DRYER.) • The vent MUST NOT be terminated beneath a mobile or manufactured home. • The vent duct material MUST BE METAL. • Do not use sheet metal screws or other refastening devices which extend into the interior of the exhaust vent. • Provide an opening with a free area of at least 25 sq. in. for introduction of outside air into the dryer room.

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108

13
Installation Instructions
REQUIREMENTS FOR ALCOVE OR
CLOSET INSTALLATION
Your dryer is approved for installation in
an alcove or closet, as stated on a label on
the dryer back.
The dryer MUST be vented to the outdoors. See
the EXHAUSTING THE DRYER section.
Minimum clearance between dryer cabinet and
adjacent walls or other surfaces is:
0
either side
3
front and rear
Minimum vertical space from floor to overhead
shelves, cabinets, ceilings, etc., is 52
.
Closet doors must be louvered or otherwise
ventilated and have at least 60 square inches
of open area equally distributed. If the closet
contains both a washer and a dryer, doors must
contain a minimum of 120 square inches of open
area equally distributed.
NOTE:
WHEN THE EXHAUST DUCT IS LOCATED AT
THE REAR OF THE DRYER, MINIMUM CLEARANCE
FROM THE WALL IS 5.5 INCHES.
BATHROOM OR BEDROOM
INSTALLATION
The dryer MUST be vented to the outdoors. See
EXHAUSTING THE DRYER.
The installation must conform with local codes or,
in the absence of local codes, with the NATIONAL
ELECTRICAL CODE, ANSI/NFPA NO. 70 (for electric
dryers) or NATIONAL FUEL GAS CODE, ANSI Z223
(for gas dryers).
MOBILE OR MANUFACTURED HOME
INSTALLATION
The installation must conform to the
MANUFACTURED HOME CONSTRUCTION & SAFETY
STANDARD, TITLE 24, PART 32–80 or, when such
standard is not applicable, with AMERICAN
NATIONAL STANDARD FOR MOBILE HOME,
NO. 501B.
The dryer MUST be vented to the outdoors with
the termination securely fastened to the mobile
home structure. (See EXHAUSTING THE DRYER.)
The vent MUST NOT be terminated beneath a
mobile or manufactured home.
The vent duct material MUST BE METAL.
Do not use sheet metal screws or other
refastening devices which extend into the interior
of the exhaust vent.
Provide an opening with a free area of at least
25 sq. in. for introduction of outside air into the
dryer room.
Wire
frame
spacer
5.5
(140 mm)
UNDERCOUNTER INSTALLATION
If an undercounter installation is desired:
No special dryer installation kit is required.
If the dryer is installed alone, a minimum of
60 square inches of open area is required.
If a washer and dryer are installed together,
a minimum of 120 square inches of open area
is required.
Washer and Dryer installed together
120
square
inches
min. open
area
Countertop and side cabinets
Dryer installed alone
60
square
inches
min.
open
area
Countertop and side cabinets