Haier HPU-18CH13 HPU-123C01 User Manual - Page 29
diametero, Liquid, 35mm1/4, 7mm1/2, Damage, flare, Crack, Partial, outside
View all Haier HPU-18CH13 HPU-123C01 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 29 highlights
Installation Manual of Room Air Conditioner Others 1. Power supply Air conditioner must use an exclusive line(over 30A) and there is not power plug with this type, the type of power supply wire is H05W-F3G4.0mm2. When installation air conditoner in a wet place, try to use a circuit breaker against Current leakage. For installation in other palces, use circuit breaker as far as possible. 2. Piping cutting and flaring Be sure to carry out deburring after cutting with a pipe cutter. Insert flaring tool to make a flare. Flare tooling die Pipe diametero Size A (mm) Liquid pipe 6.35mm(1/4") 0.8 -1.5 Gas pipe 12.7mm(1/2") 1.2 -2.0 Correct Incorrect V '. 11 151 JO Ci? vieo -ts. Lean Damage of flare Crack Partial Too outside Installation inspection and test run: Please operate unit according to this Manual. Items to be checked during test run. Please made a " .V" in " CI " CI Are there any gas leakage? El How is insulation at piping connection carried out? CI Are electric wires of indoor and outdoor unit firmly inserted into terminal block? El Is electric wiring of indoor and outdoor securely fixed? CI Is drainage securely carried out? CI Is earth line(grounding) securely connected? CI Is power supply voltage abided by the code? CI Is there any noise? CI Is control display normal? CI Is cooling operation normal? CI Is room temp. regulator normal? 28