- HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 1
Site Preparation Guide HP Integrity rx2620 Server Regulatory Model Number: RSVLA-0403 Manufacturing Part Number: AD117-9005A First Edition August 2006 U.S.A. © Copyright 2006 Hewlett-Packard Development Company, L.P. - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 2
accompanying such products and services. Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial errors or omissions contained herein. Printed in the USA. Intel, Intel Inside, Itanium, and the Intel Inside logo are trademarks - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 3
15 Environmental Specifications 15 2. General Site Preparation Guidelines Electrical Factors 17 Computer Room Safety 17 Power Consumption 18 Electrical Load Requirements (Circuit Breaker Sizing 18 Power Quality 18 Distribution Hardware 19 Grounding Systems 20 System Installation Guidelines - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 4
Contents Sample of an Installation Schedule 34 Sample Site Inspection Checklist 35 Delivery Survey 38 Glossary 41 Index 43 4 - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 5
9 Table 2. HP-UX 11i Releases 11 Table 1-1. Hardware Specifications 13 Table 1-2. Server Component Dimensions 13 Table 1-3. System Power Specifications 14 Table 1-4. Additional Component Power Consumption 15 Table 1-5. Environmental Specifications (system processing unit with hard disk 15 - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 6
Tables 6 - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 7
Figures Figure 2-1. Raised Floor Metal Strip Ground System 22 Figure 2-2. Delivery Survey (Part 1 39 Figure 2-3. Delivery Survey (Part 2 40 7 - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 8
Figures 8 - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 9
service providers, system administrators, and HP support personnel. This document is not a tutorial. New and Changed Information in This Edition This guide has been updated with: • This document is being updated as part of a processor upgrade to the HP Integrity rx2620 server. Publishing - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 10
injury. CAUTION A caution provides information required to avoid losing data or avoid losing system functionality. NOTE A note highlights useful information such as restrictions, recommendations, or important details about HP product features. Book Title The title of a book. On the Web and on - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 11
11.20 B.11.22 B.11.23 Release Name HP-UX 11i v1 HP-UX 11i v1.5 HP-UX 11i v1.6 HP-UX 11i v2.0 Supported Processor Architecture PA-RISC Intel® Itanium® Intel Itanium Intel Itanium Related Documents You can find other information on HP server hardware management, Microsoft® Windows®, and diagnostic - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 12
your comments concerning this document. We are truly committed to providing documentation that meets your needs. Please send comments to: [email protected]. Please include title, manufacturing part number, and any comment, error found, or suggestion for improvement you have concerning this - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 13
system specification for the hp Integrity rx2620 Server. Table 1-1 Hardware Specifications Component Micro-processors Memory HDDs PCI Slots Internal Core I/O External Core I/O Optical Device Power Supply rx2620 1 or 2 Itanium dual core processors, 1.4 GHz/12 MB, or 1.6GHz/18 MB - 533 MHz front - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 14
the building installation earth or, if supplied by a separately derived system, at the supply transformer or motor-generator set grounding point. Electrical Specifications This section provides electrical specifications for the your HP Server. System Power Specifications Available power (output - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 15
an HP support representative. Step 3. Reconnect the power cord, then reboot the system. If an overload occurs twice, there is an undetected short circuit somewhere. When you use the front panel's power button to turn off the server, power consumption falls below the low power consumption, but - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 16
Specifications Table 1-5 Environmental Specifications (system processing unit with hard disk) Parameter Value Storage humidity Acoustic Noise Emission (ISO 7779) Typical configuration (disk idle)b Maximum configuration (disk idle)c 90% relative (noncondensing) at + 65° C Sound Power - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 17
specific or area-specific electrical codes and guidelines. Proper design and installation of a power distribution system for an hp Integrity rx2620 Server Power consumption • Electrical load requirements (circuit breaker sizing) • Power quality • Distribution hardware • System installation - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 18
connectors to 80% of their RMS current ratings. Power Quality The hp Integrity rx2620 Server is designed to operate over a wide range of voltages and frequencies. The server is tested and shown to comply with EMC Specification EN55024. However, damage can occur if these ranges are exceeded. Severe - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 19
. Therefore, adherence to the following guidelines provides the best possible performance of power distribution systems for HP computer equipment: • Dedicated power source-Isolates an hp Integrity rx2620 Server power distribution system from other circuits in the facility. • Missing-phase and low - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 20
constructed of rigid galvanized steel. Grounding Systems IT Power System This product has not been evaluated for connection to an IT power system (an AC distribution system having no direct connection to earth according to IEC 60950). An hp Integrity rx2620 Server requires two methods of grounding - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 21
investigated. Cabinet Performance Grounding (High Frequency Ground) Signal interconnects between system cabinets require high system cabinet to the site grounding grid (customer-supplied). When connecting this ground, ensure that the raised floor is properly grounded for high frequency. Power panels - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 22
HP computer equipment). The use of conductive floor tiles with this style of grid further enhances ground performance. The structure needs to be mechanically bonded to a known good ground point. Figure 2-1 Raised Floor Metal Strip Ground System Ground wire Floor panel to power panel each end of - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 23
problems, such as erratic equipment operation. A high impedance connection overheats and sometimes causes fire or high temperatures that can destroy hard-to-replace components such as distribution panels or system elements can affect an hp Integrity rx2620 Server installation: • Computer room - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 24
top of the hp Integrity rx2620 Server cabinet to the fire sprinkler heads. Cooling Requirements Air conditioning equipment requirements and recommendations are described in the following sections. Basic Air Conditioning Equipment Requirements The cooling capacity of the installed air conditioning - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 25
floor manufacturer) should be located around the front of the system cabinets. Supply air emitted though the perforated floor panels is then available near the cooling air intake vents of the hp Integrity rx2620 Server cabinets. • Ceiling plenum air distribution system-Supply air is ducted into the - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 26
air downward around the front of the hp Integrity rx2620 Server cabinets. The supply air is then available near the cooling air intake vents of the hp Integrity rx2620 Server cabinets. Air Conditioning System Specifications All air conditioning equipment, materials, and installation must comply with - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 27
are eight times larger than the clearance between disk drive read/write heads and the disk surface. • of some raised floor tiles. Although this problem is relatively rare, it may be an issue for metallic particulate contamination before installation of electronic equipment. Electrostatic Discharge - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 28
to minimize possible ESD-induced failures in the computer room: • Maintain recommended humidity level and airflow rates in the computer room. • Install conductive flooring (conductive adhesive must be used when laying tiles). • Use conductive wax if waxed floors are necessary. • Ensure that all - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 29
toward raised floor installations. NOTE An appropriate floor system consultant should verify any floor system under consideration for an hp Integrity rx2620 Server installation. Raised Floor Loading Raised floor loading is a function of the manufacturer's load specification and the positioning - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 30
raised floor system that is satisfactory for the installation of an hp Integrity rx2620 Server. Based on specific information provided by HP, Tate Access Floors has approved its Series 800 all-steel access floor with bolt-together stringers and 24 in. (61.0 cm) by 24 in. (61.0 cm) floor panels. In - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 31
problems. Magnetic tape storage media is damaged if exposed to direct sunlight. Also, the heat generated by sunlight places an additional load on the cooling system. Space Requirements This section contains information about space requirements for an hp Integrity rx2620 Server side panels must not - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 32
areas for power wiring and air conditioning filters • Equipment cable routing Conversion Factors and Formulas The conversion factors provided here are intended to ease data calculation for systems that do not conform specifically to the configurations listed in this Site Preparation Guide. Listed - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 33
- 1 ft. = 0.305 m - 1 CFM = 1.7m3/h • kVA Conversions Three phase kVA = V × A × √3 ⁄ 1000 • Single phase kVA = V × A ⁄ 1000 Formulas • kVA = Voltage x Current (amps) • Watts = VA x PF • BTU = Watts x 3.41 General Site Preparation Guidelines Conversion Factors and Formulas Chapter 2 33 - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 34
made with an Hewlett-Packard site preparation specialist to resolve any last minute problems NOTE Not all installations follow a schedule like the one noted above. Sometimes, an hp Integrity rx2620 Server is purchased through another vendor, which can preclude a rigid schedule. Other conditions - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 35
a completed floor plan? 2. Is there adequate space for maintenance needs? Front 36 in (91.4 cm) minimum, rear 36 in (91.4 cm) installed and in good condition? 6. Is the raised floor adequate for equipment loading? 7. Are there channels or cutouts for cable routing? 8. Is there a remote console - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 36
for servicing needs? (for example, vacuuming) 15. Does the input voltage correspond to equipment specifications? 15A Is dual source power used? If so, identify type(s) and evaluate grounding. 16 Does the input frequency correspond to equipment specifications? 17. Are lightning arrestors installed - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 37
maintained at 40% to 60% at 35° C noncondensing? 30. Are air conditioning filters installed and clean? Storage No. Area or condition Yes No 31. Are cabinets available for tape 33 Are personnel enrolled in the System Administrator's Course? 34 Is on-site training required? Comment or Date Chapter - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 38
or recommendations form. The following list gives examples of special instructions or issues: • Packaging restrictions at the facility, such as size and weight limitations • Special delivery procedures • Special equipment required for installation, such as tracking or hoists • What time the facility - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 39
General Site Preparation Guidelines Delivery Survey Figure 2-2 Delivery Survey (Part 1) DELIVERY CHECKLIST DOCK DELIVERY Is dock large enough for a semitrailer? Yes No ___________ Circle the location of the dock and give street name if different than address. North West East South - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 40
General Site Preparation Guidelines Delivery Survey Figure 2-3 Delivery Survey (Part 2) ELEVATOR Fill in the following information if an elevator is required to move equipment. Capacity (lb. or kg Depth Height Width Height Dept Widt STAIRS Please list number of flights and stairway - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 41
card or adapter. Btu/h The abbreviation for CompactPCI The newest specification for PCI-based system, the electrical power connection, excessive heat, or blocking the natural airflow, and connecting wires or cables. The FCC (Federal Communications Commission) regulates a portion of this problem - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 42
will experience this level of power consumption. Tonnage The unit of measure used in air conditioning to describe the heating or cooling capacity of a system. One ton of heat represents the amount of heat needed to melt one ton (2,000 lbs.) of ice in one hour. 12,000 Btu/hr. equals one ton of - HP Integrity rx2620 | Site Preparation Guide. First Edition - HP Integrity rx262 - Page 43