System Specifications Environmental Specifications Environmental Specifications This section provides the temperature/humidity requirements, noise emission, and air flow specifications for the HP Server. Temperature and Humidity Specifications Ambient intake air temperature is often different from ambient room temperature; you should measure the operating temperature and humidity directly in front of the cabinet cooling air intakes rather than just checking ambient room conditions. Table 1-6 Computer Environment Parameter Temperature Relative humidity Operating Range 5oC to 35oC (up to 5,000 feet) 15% to 80% at 35oC noncondensing Recommended Operating Range Maximum Rate of Change 20oC to 25oC (up to 5,000 feet) 10oC/hr with tape 20oC/hr without tape 40% to 60% at 35oC noncondensing 30% per hour noncondensing Non-Operating Range -40oC to +70oC NOTE Operating ranges refer to the ambient air temperature and humidity measured at the cabinet cooling air intake vents. Acoustic Noise Specification The acoustic noise specification for the HP Server is as follows: • < 60 db LpA (sound pressure level at bystander position) The above level is appropriate for dedicated computer room environments, not office environments. Care should be taken to understand the acoustic noise specifications relative to operator positions within the computer room or when adding HP Servers to computer rooms with existing noise sources. Air Flow The recommended cabinet air intake temperature is between 68oF and 77oF (20oC and 25oC) at 960 CFM. Chapter 1 9

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46

System Specifications
Environmental Specifications
Chapter 1
9
Environmental Specifications
This section provides the temperature/humidity requirements, noise emission, and air flow specifications for
the HP Server.
Temperature and Humidity Specifications
Ambient intake air temperature is often different from ambient room temperature; you should measure the
operating temperature and humidity directly in front of the cabinet cooling air intakes rather than just
checking ambient room conditions.
NOTE
Operating ranges refer to the ambient air temperature and humidity measured at the cabinet
cooling air intake vents.
Acoustic Noise Specification
The acoustic noise specification for the HP Server is as follows:
< 60 db LpA (sound pressure level at bystander position)
The above level is appropriate for dedicated computer room environments, not office environments.
Care should be taken to understand the acoustic noise specifications relative to operator positions within the
computer room or when adding HP Servers to computer rooms with existing noise sources.
Air Flow
The recommended cabinet air intake temperature is between 68
o
F and 77
o
F (20
o
C and 25
o
C) at 960 CFM.
Table 1-6
Computer Environment
Parameter
Operating
Range
Recommended
Operating
Range
Maximum Rate of
Change
Non-Operating
Range
Temperature
5
o
C to 35
o
C (up
to 5,000 feet)
20
o
C to 25
o
C (up
to 5,000 feet)
10
o
C/hr with tape
20
o
C/hr without tape
-40
o
C to +70
o
C
Relative
humidity
15% to 80% at
35
o
C
noncondensing
40% to 60% at
35
o
C
noncondensing
30% per hour
noncondensing