HP LH4r HP Netserver LXr 8500 Reference Guide - Page 21

Table 2-2. LXr 8500 Plugs and Receptacles Reference

Page 21 highlights

Chapter 2 Rack Cabling References Table 2-2. LXr 8500 Plugs and Receptacles Reference LXr 8500 Jumper Cord RackStorage/12 and /12FC and PDU Jumper Cord PDU Model No. Can PDUs be "Daisy Chained"? PDU Linecord style PDU linecord for recommended UPS Alternate PDU linecords for installations without a UPS UPS APC Model Number APC Redundant Switch between PDU and Branch Circuits (No UPS) Redundant Switch between UPS and Branch Circuit 208 VAC Mains included C19 to C20, 2.5 m E7742A, 90 inch (2.5 m), C13 to C14 E7671A (16 Amp) E7672A (16 amp, cord, and 10 amp) Yes, 10 amp plugs into 16 amp (use to extend the number of receptacles)1 Detachable E7803A, 4.5m, with NEMA L6-20P plug to C19 E7803A, 4.5m, NEMA L620P to C19 plug E7805A 4.5 m with NEMA L6-30P to C19 NS3000RMT3U SU045-1 with captive L6-20P line cords and E7803A, 4.5 m, L6-20P to C19 to PDU3 SU045-1 with captive line cords, captive UPS L6-20 P connects to L6-20R in switch3 230/240V Mains included C19 to C20, 2.5 m E7742A, 90 inch (2.5 m), C13 to C14 E7671A (16 Amp) E7672A (16 amp, cord, and 10 amp) Yes, 10 amp plugs into 16 amp (use to extend the number of receptacles) 1 Detachable E7804A, 4.0m, with IEC C20 to C19 plug, E7806A, 4.5 m, C19 to unterminated E7804A, 4.5 m, C20 to C19 E7809A, 4.5 m, CEE 7/7 C192 NS2200RMI3U or NS3000RMI3U SU044-1, C20 inputs, country-specific C19 cords, and E7804A, 4 m, C20 to C19 jumper cord to PDU4 SU044-1, C20 inputs, country-specific C19 cords, and E7804A, 4 m C20 to C19 jumper cord to UPS4 Note 1. Limit the 10-amp PDU to 10 amps of capacity, plug it into the 16-amp PDU, and limit both together to 16 amps of capacity. Note 2. The CEE 7/7 cord is fused for 13-amp loads, and limits the PDU to 13 amps of total supply. Note 3. The circuit load should be limited to 3000 VA when this switch is used. Note 4. The circuit load should be limited to 3000 VA when this switch is used. 17

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59

Chapter 2
Rack Cabling References
17
Table 2-2. LXr 8500 Plugs and Receptacles Reference
208 VAC Mains
230/240V Mains
LXr 8500 Jumper Cord
included
C19 to C20, 2.5 m
included
C19 to C20, 2.5 m
RackStorage/12 and /12FC
and PDU Jumper Cord
E7742A, 90 inch (2.5 m), C13
to C14
E7742A, 90 inch (2.5 m),
C13 to C14
PDU Model No.
E7671A (16 Amp)
E7672A (16 amp, cord, and
10 amp)
E7671A (16 Amp)
E7672A (16 amp, cord, and
10 amp)
Can PDUs be "Daisy
Chained"?
Yes, 10 amp plugs into 16
amp (use to extend the
number of
receptacles)
1
Yes, 10 amp plugs into 16
amp (use to extend the
number of receptacles)
1
PDU Linecord style
Detachable
Detachable
PDU linecord for
recommended UPS
E7803A, 4.5m,
with NEMA
L6-20P plug to C19
E7804A, 4.0m, with IEC
C20 to C19 plug,
E7803A, 4.5m, NEMA L6-
20P to C19 plug
E7806A, 4.5 m, C19 to
unterminated
E7805A 4.5 m with NEMA
L6-30P to C19
E7804A, 4.5 m, C20 to C19
Alternate PDU linecords
for installations without a
UPS
E7809A, 4.5 m, CEE 7/7 -
C19
2
UPS APC Model Number
NS3000RMT3U
NS2200RMI3U or
NS3000RMI3U
APC Redundant Switch
between PDU and Branch
Circuits (No UPS)
SU045-1 with captive L6-20P
line cords and E7803A, 4.5 m,
L6-20P to C19 to PDU
3
SU044-1, C20 inputs,
country-specific C19 cords,
and E7804A, 4 m, C20 to
C19 jumper cord to PDU
4
Redundant Switch between
UPS and Branch Circuit
SU045-1 with captive line
cords, captive UPS L6-20 P
connects to L6-20R in switch
3
SU044-1, C20 inputs,
country-specific C19 cords,
and E7804A, 4 m C20 to
C19 jumper cord to UPS
4
Note 1. Limit the 10-amp PDU to 10 amps of capacity, plug it into the 16-amp PDU, and
limit both together to 16 amps of capacity.
Note 2. The CEE 7/7 cord is fused for 13-amp loads, and limits the PDU to 13 amps of total
supply.
Note 3. The circuit load should be limited to 3000 VA when this switch is used.
Note 4. The circuit load should be limited to 3000 VA when this switch is used.