HP LH4r HP Netserver LXr 8500 Reference Guide - Page 39

R, providing 208VAC. The E7671A PDU connects to the UPS viadetachable

Page 39 highlights

Chapter 3 Procedure for Connecting and Routing Cables to the LXr 8500 Alternate 208 VAC Power Configurations In the 208 VAC case, without a UPS, make sure your power system has the capacity to support the power and current needs of the components you will power. (See the section entitled "Site Preparation: Circuit Breakers.) If capacity is adequate, plug the PDU into a 208 V, L6-20 receptacle. Table 3-1. 208 VAC Components Component1 208 VAC PDU Model E7671A or E7672A Power (VA) N/A Power (W) N/A Current (A)2 max 16 HP NetServer D7057A, 500 MHz, 512K Cache 1121 1077 5.6 LXr 85003 D7133A, 500 MHz, 1MB Cache D7058A, 500 MHz, 2MB Cache HP NetServer Rack Storage/12 is D5989A 547 538 2.6 Mass Storage Rack Storage/12FC is D5991A Unit HP Console Switch J1497B 42 29 0.2 Note 1 More ratings are listed in Table 2-6. For a full list of power ratings, see the rack configuration utilities (for instance, Rack Assistant) on the HP Web Site. Note 2 Indicated current ratings are for use in selecting PDU and UPS components and may not reflect actual measured amounts. Note 3 When ordered through select express, the D7057A becomes D7062AV, the D7133A becomes D7063AV, and the D7058A becomes D7134AV. Description of the Recommended 208 VAC Configuration Figure 3-5 shows a UPS connected to the power mains through a captive cord terminated with an L6-20P plug. The UPS has five receptacles for use in the rack: two (on the right rear) NEMA 5-15 providing 110 VAC, two L6-20R, and one L630R, providing 208VAC. The E7671A PDU connects to the UPS via a detachable cord with an L6-20P plug. This cord connects to the PDU with an IEC 320 C-19 plug. The 208 VAC PDU has two IEC 320, C-19 and six IEC 320, C-13 receptacles. A second PDU (E7670A) is available, which can be daisy-chained to the 16-amp unit, providing ten more C-13 receptacles. 35

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59

Chapter 3
Procedure for Connecting and Routing Cables to the LXr 8500
35
Alternate 208 VAC Power Configurations
In the 208 VAC case, without a UPS, make sure your power system has the
capacity to support the power and current needs of the components you will
power. (See the section entitled “Site Preparation: Circuit Breakers.) If capacity is
adequate, plug the
PDU into a 208 V, L6-20 receptacle.
Table 3-1. 208 VAC Components
Component
1
Model
Power
(VA)
Power
(W)
Current
(A)
2
208 VAC
PDU
E7671A or E7672A
N/A
N/A
max 16
HP NetServer
LXr 8500
3
D7057A, 500 MHz, 512K Cache
D7133A, 500 MHz, 1MB Cache
D7058A, 500 MHz, 2MB Cache
1121
1077
5.6
HP NetServer
Mass Storage
Unit
Rack Storage/12 is D5989A
Rack Storage/12FC is D5991A
547
538
2.6
HP Console
Switch
J1497B
42
29
0.2
Note 1
More ratings are listed in Table 2-6. For a full list of power ratings, see the rack
configuration utilities (for instance, Rack Assistant) on the HP Web Site.
Note 2
Indicated current ratings are for use in selecting PDU and UPS components and
may not reflect actual measured amounts.
Note 3
When ordered through select express, the D7057A becomes D7062AV, the
D7133A becomes D7063AV, and the D7058A becomes D7134AV.
Description of the Recommended 208 VAC Configuration
Figure 3-5 shows a UPS connected to the power mains through a captive cord
terminated with an L6-20P plug. The UPS has five receptacles for use in the rack:
two (on the right rear) NEMA 5-15 providing 110 VAC, two L6-20R, and one L6-
30R, providing 208VAC. The E7671A PDU connects to the UPS via a detachable
cord with an L6-20P plug. This cord connects to the
PDU with an IEC 320 C-19
plug. The 208 VAC
PDU has two IEC 320, C-19 and six IEC 320, C-13
receptacles. A second PDU (E7670A) is available, which can be daisy-chained to
the 16-amp unit, providing ten more C-13 receptacles.