HP R1500 HP R/T3000 G2 UPS User Guide - Page 42

Configuring the UPS

Page 42 highlights

NOTE: If the On and Off buttons are simultaneously pressed, the Off button has priority over the On button. Button On Assertion time 0.5 seconds Audible alarm Mode before assertion Every 0.5 seconds Standby until the button is released Operate Auto-Bypass Converter Off Off 3 seconds Every 0.5 seconds Operate until the button is released Standby Battery Auto-bypass Self Test 0.5 seconds 3 seconds Continuously Battery Start 0.5 seconds Battery Start 3 seconds and On Continuously On and Self 3 seconds Test Continuously Any Any Any UPS off Any Utility present ? Yes Yes Yes Yes Yes Yes No Yes or No Yes or No Yes or No Yes or No No Yes or No Action Energizes the load and resets the bypass entry count to 0 Resets the bypass entry count to 0 Clears the UPS On audible alarms, resets the bypass entry count to 0, and attempts to transfer to Operate mode Clears the UPS On audible alarms, resets the bypass entry count to 0, and attempts to transfer to Operate mode Transfers to Standby mode, and power to the load ceases No action Powers down the UPS, and power to the load ceases Transfers to Standby mode or Converter Off mode, and power to the load ceases Silences audible alarms after 0.5 seconds Initiates a self-test No action Transfers to battery power, and begins powering the load Enters or exits Configuration mode Configuring the UPS The UPS automatically detects the number of ERMs connected. In Configure mode, the LED front panel display changes function to enable modification of the UPS parameters. Each LED is associated with a different parameter. Available settings Nominal voltage setting Parameter Associated LED 100/204 Nom Self Test Explanation (when LED is illuminated) Nominal output voltage is 100 V for a low voltage model and 204 V for a high voltage model UPS operations 42

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80

UPS operations 42
NOTE:
If the On and Off buttons are simultaneously pressed, the Off button has priority over the
On button.
Button
Assertion
time
Audible alarm
Mode before
assertion
Utility
present ?
Action
On
0.5 seconds
Every 0.5 seconds
until the button is
released
Standby
Yes
Energizes the load and
resets the bypass entry count
to 0
Operate
Yes
Resets the bypass entry count
to 0
Auto-Bypass
Yes
Clears the UPS On audible
alarms, resets the bypass
entry count to 0, and
attempts to transfer to
Operate mode
Converter Off
Yes
Clears the UPS On audible
alarms, resets the bypass
entry count to 0, and
attempts to transfer to
Operate mode
Off
3 seconds
Every 0.5 seconds
until the button is
released
Operate
Yes
Transfers to Standby mode,
and power to the load
ceases
Standby
Yes
No action
Battery
No
Powers down the UPS, and
power to the load ceases
Auto-bypass
Yes or No
Transfers to Standby mode
or Converter Off mode, and
power to the load ceases
Self Test
0.5 seconds
Any
Yes or No
Silences audible alarms after
0.5 seconds
3 seconds
Continuously
Any
Yes or No
Initiates a self-test
Battery Start
0.5 seconds
Any
Yes or No
No action
Battery Start
and On
3 seconds
Continuously
UPS off
No
Transfers to battery power,
and begins powering the
load
On and Self
Test
3 seconds
Continuously
Any
Yes or No
Enters or exits Configuration
mode
Configuring the UPS
The UPS automatically detects the number of ERMs connected.
In Configure mode, the LED front panel display changes function to enable modification of the UPS
parameters. Each LED is associated with a different parameter.
Available settings
Parameter
Associated LED
Explanation (when LED is illuminated)
Nominal voltage
setting
100/204 Nom
Self Test
Nominal output voltage is 100 V for a low
voltage model and 204 V for a high voltage
model