HP R1500 HP R/T3000 G2 UPS User Guide - Page 62
Power protection specifications, Output tolerance specifications, Battery specifications
View all HP R1500 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 62 highlights
UPS model - - - R/T3000 INTL - - - Load segment - 2 - 1 - 2 - Output receptacles 1 x L6-20R 3 x IEC-320-C13 1 x IEC-320-C19 3 x IEC-320-C13 1 x IEC-320-C19 3 x IEC-320-C13 1 x IEC-320-C19 Power protection specifications UPS model VA R/T3000 NA/JPN R/T3000h NA/JPN R/T3000 INTL 2880 / 2400 3300 3300 Nominal power rating (W) 2700 / 2250 3000 3000 Nominal voltage setting 120/100 204 230 Output tolerance specifications Source of power Utility power (nominal range) Battery power Regulation -10% to +6% of nominal output voltage rating (within the guidelines of the Computer Business Equipment Manufacturers Association) ±5% of nominal output voltage rating Output feature specifications Feature Online efficiency Voltage wave shape Surge suppression Noise filtering Specification 94% nominal input voltage Sine wave; 5% THD with typical PFC load 300J via MOVs EN 55022 line filter for normal and common mode use Battery specifications Feature Type Voltage Specification 12 V, 5 AH, sealed, maintenance-free, rechargeable, valve regulated lead-acid batteries with a 3-5 year service life at 25°C (77°F). The battery modules have a battery string voltage of 120 V. Specifications 62