Specifications, UPS physical specifications - g2 intl ups
View all HP R1500 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 36 highlights
Specifications UPS physical specifications Parameter Height Depth Width Weight Value 4.5 cm (1.75 in) 57.8 cm (22.8 in) 44 cm (17.3 in) 23 kg (50.5 lb) UPS input specifications NOTE: An asterisk (*) indicates the default setting. UPS model R1500 G2 NA R1500 G2 JPN/TWN R1500 G2 INTL Utility voltage frequency (auto-sensing) 50/60 Hz 50/60 Hz 50/60 Hz Available settings utility voltage ("Selecting the UPS voltage configuration" on page 19) (VAC) 110, 120* 100*, 110 220, 230*, 240 Branch circuit rating (A) Line cord 15 or 20 15 or 20 16 Power cord with NEMA 5-15 plug Power cord with NEMA 5-15 plug (BSMI approved for TWN) IEC-320-C14 power inlet UPS output specifications UPS model R1500 G2 NA/JPN/TWN R1500 G2 INTL Output receptacles 4 x NEMA 5-15 4 x IEC-320-C13 Specifications 36