Floor Surface and Strength Note The customer is strictly responsible for surface and load-bearing compliance. When planning the print production area, it is important to ensure that the floor surface is solid, smooth, level, and free from any holes or indentations. Floor covering material must be non-flammable, durable and easy to clean. The floor of the print production area, as well as that on machine's way from the unpacking area, must be strong enough to support the entire weight of the printer, including all accompanying equipment. Floor load-bearing capabilities for the building in which the FB7600 printer is to be installed require consulting a construction engineer. Note Installation of the machine loader requires drilling eight (8) holes into the floor. The following information is provided to assist the engineer: • The floor must be strong enough to support the machine, loaded with 300 kg, while standing on its 6 supporting pads. • The machine weight is 5560 kg (12258 lb). • The vacuum unit weight is 367 kg (809 lb). • A single supporting pad foot print is 115 x 115 mm (4.5 x 4.5 in.) • The floor must be leveled with a maximum incline of 0.2%. Danger If the floor surface in the print production area is to be tiled, the tiles should be firmly cemented into position with tile cement applied to the full area of each tile base (and not just in the center). Tiles must be non-flammable (made of marble, stone, etc.). Wood flooring is not allowed. So you can keep the tiles section, just mention the tiles must be non-flammable. Failure to do this may not provide adequate support to heavy system components and could result in personal injury or damage to the printer during installation. Electrical Requirements This section provides the electrical specifications of the HP Scitex FB7600 printer. Every system may be adapted to the mains power voltage of the country of installation. • As a safety precaution, the FB7600 printer should be hard wired to a wall- mounted circuit breaker (or PDU). This outlet should be suitably rated to meet the power requirements of the FB7600 printer, and should be in accordance with the wiring standards of the country of installation. • All electrical cables that are stretched between the PDU and the machine components should be protected against mechanical hazard using suitable protection. 28 HP Scitex Industrial Presses Essential Health and Safety Instructions

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52

28
HP Scitex Industrial Presses Essential Health and Safety Instructions
Floor Surface and Strength
Note
The customer is strictly responsible for surface and load-bearing compliance.
When planning the print production area, it is important to ensure that the
floor surface is solid, smooth, level, and free from any holes or indentations.
Floor covering material must be non-flammable, durable and easy to clean.
The floor of the print production area, as well as that on machine's way from
the unpacking area, must be strong enough to support the entire weight of the
printer, including all accompanying equipment.
Floor load-bearing capabilities for the building in which the FB7600 printer is
to be installed require consulting a construction engineer.
Note
Installation of the machine loader requires drilling eight (8) holes into the floor.
The following information is provided to assist the engineer:
The floor must be strong enough to support the machine, loaded with 300
kg, while standing on its 6 supporting pads.
The machine weight is 5560 kg (12258 lb).
The vacuum unit weight is 367 kg (809 lb).
A single supporting pad foot print is 115 x 115 mm (4.5 x 4.5 in.)
The floor must be leveled with a maximum incline of 0.2%.
Danger
If the floor surface in the print production area is to be tiled, the tiles should be firmly
cemented into position with tile cement applied to the full area of each tile base (and not
just in the center). Tiles must be non-flammable (made of marble, stone, etc.).
Wood flooring is not allowed. So you can keep the tiles section, just mention the tiles
must be non-flammable.
Failure to do this may not provide adequate support to heavy system components and
could result in personal injury or damage to the printer during installation.
Electrical Requirements
This section provides the electrical specifications of the HP Scitex FB7600
printer. Every system may be adapted to the mains power voltage of the
country of installation.
As a safety precaution, the FB7600 printer should be hard wired to a wall-
mounted circuit breaker (or PDU). This outlet should be suitably rated to
meet the power requirements of the FB7600 printer, and should be in
accordance with the wiring standards of the country of installation.
All electrical cables that are stretched between the PDU and the machine
components should be protected against mechanical hazard using suitable
protection.