Honeywell PRO22IC Installation Manual - Page 13

Suggested Installation Sequence, Specification Summary

Page 13 highlights

PRO-2200 Intelligent Controller PRO22IC Installation Guide 13 Suggested Installation Sequence 1. Set Jumpers and the DIP-switch per this installation guide. 2. Install the PRO22EN and/or PRO22M4 option boards per the appropriate installation guide. 3. Mount this board in the appropriate enclosure-If this board is being mounted in a rack the component side of the board is on right when facing the rack. 4. Connect the communications and power supply to the circuit boards with the Power Supply Harness. WARNING: DO NOT CONNECT THE POWER SUPPLY TO THE AC SOCKET UNTIL ALL WIRING HAS BEEN INSTALLED AND RECHECKED. 5. Connect wiring to alarm input sensors or install jumper wire as appropriate. 6. Connect communications wiring to I/O boards as appropriate. 7. Recheck wiring for correct connections and continuity. 8. Run communication wiring to PC, central station, modem or printer. 9. Recheck communication wiring for correct connections and continuity. 10. Connect the Power Supply Cord for proper connections and power. 11. Setup the panel controls using the host software. Note: You may install a map of eight boards per Intelligent Controller. It is recommended for maximum performance, that the I/O Reader boards be installed in a configuration that doesn't exceed eight boards per port. Specification Summary The controller is for use in low voltage, class 2 circuit only. Primary power: DC input12 VDC ±10%, 400mA (550mA with PRO22EN)(401mA with PRO22M4) Memory and Clock Backup: 3 V Lithium, type BR2325 Data memory: 1Mb standard (4Mb with optional memory module, J3) Ports: 1 2-3 RS-232 or RS-485 (9,600 to 38,400 BPS, asynchronous) - optional Ethernet board RS-485 (9,600 to 38,400 BPS, asynchronous) Inputs: two non-supervised, dedicated function (Tamper and Power Fail Detect) Wire requirements: Power RS-485 24 AWG RS-232 24 AWG Alarm Input 1 twisted pair, 18 AWG 4,000 ft (1,200m) max, 2 twisted pair(s) with shield (120Ω, 23pF, Belden 9842 or equivalent) 25 ft (7.6m) max. 1 twisted pair, 30 ohms max. Environmental: Temperature Humidity 0 to 49 °C, operating -55 to +85 °C, storage 0 to 85% RHNC

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16

PRO-2200 Intelligent Controller PRO22IC
13
Installation Guide
Suggested Installation Sequence
1.
Set Jumpers and the DIP-switch per this installation guide.
2.
Install the PRO22EN and/or PRO22M4 option boards per the appropriate
installation guide.
3.
Mount this board in the appropriate enclosure—If this board is being mounted in a
rack the component side of the board is on right when facing the rack.
4.
Connect the communications and power supply to the circuit boards with the Power
Supply Harness.
WARNING:
DO NOT CONNECT THE POWER SUPPLY TO THE AC SOCKET UNTIL
ALL
WIRING HAS BEEN INSTALLED AND RECHECKED.
5.
Connect wiring to alarm input sensors or install jumper wire as appropriate.
6.
Connect communications wiring to I/O boards as appropriate.
7.
Recheck wiring for correct connections and continuity.
8.
Run communication wiring to PC, central station, modem or printer.
9.
Recheck communication wiring for correct connections and continuity.
10.
Connect the Power Supply Cord for proper connections and power.
11.
Setup the panel controls using the host software.
Note:
You may install a map of eight boards per Intelligent Controller. It is
recommended for maximum performance, that the I/O Reader boards be installed in
a configuration that doesn't exceed eight boards per port.
Specification Summary
The controller is for use in low voltage, class 2 circuit only.
Primary power
:
DC input12 VDC ±10%, 400mA (550mA with PRO22EN)(401mA with PRO22M4)
Memory and Clock Backup
:
3 V Lithium, type BR2325
Data memory
:
1Mb standard (4Mb with optional memory module, J3)
Ports
:
1
RS-232 or RS-485 (9,600 to 38,400 BPS, asynchronous) – optional Ethernet board
2-3
RS-485 (9,600 to 38,400 BPS, asynchronous)
Inputs
:
two non-supervised, dedicated function (Tamper and Power Fail Detect)
Wire requirements
:
Power
1 twisted pair, 18 AWG
RS-485 24 AWG
4,000 ft (1,200m) max,
2 twisted pair(s) with shield (120
, 23pF, Belden 9842 or
equivalent)
RS-232 24 AWG
25 ft (7.6m) max.
Alarm Input
1 twisted pair, 30 ohms max.
Environmental
:
Temperature
0 to 49 °C, operating -55 to +85 °C, storage
Humidity
0 to 85% RHNC