Honeywell PRO22IC Installation Manual - Page 14

Wiring Diagram

Page 14 highlights

14 Installation Guide PRO-2200 Intelligent Controller PRO22IC Wiring Diagram Tamper Switch (In Close Position when Cabinet Door Is Closed) +12VDC Power Supply PWR + PWR - No Charging - C No Charging - N/C Low Battery - C Input ? Common Input ? Low Battery - N/C + DC Output - Do NOT tie PWR- to chassis GND ! Tamper 1 Switch Common 2 Power Fail 3 CONTROLLER BOARD Battery Lithium 3V Any Supervised Input On Any Adjacent Rack Mounted Board (OPTIONAL) LAN Card Connector J2 RS 485 or RS 232 Com Bus Cable NC 485-Com +, or, Com-TXD 1 485-Com -, or, Com-RXD 2 Com-RTS 3 Com-CTS 4 Com-Gnd 5 Note Connect to chassis GND at one side ONLY! RS 485 Com Bus Cable To Other Panel NC Note Connect to chassis GND at one side ONLY! CardRack PWR & Com Harness 485-Com + 485-Com - 1 Com-Gnd 2 3 485-Com + 1 485-Com - 2 Com-Gnd 3 PWR + 1 PWR - 2 Port 2 Port 1 ABC J14 123 J4 J5 J6 J9 U1 Configuration Dip Switches S1 8 7 6 58 4 3 2 1 J3 J12 RS-485 Termination J13 PROM U1 1 Memory Expansion Connector Port 3 Power Note: For N-485 Communication Connections, twist the blue pair together and use as the common; use the orange pair as your data pair, observing polarity. Connect the external drain shield to the appropriate earth ground on one end.

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16

14
PRO-2200 Intelligent Controller PRO22IC
Installation Guide
Wiring Diagram
CONTROLLER
BOARD
485-Com +
485-Com -
Com-Gnd
RS 485
Com
Bus Cable To
Other Panel
Power
RS-485
Termination
A
B
C
1
2
3
1
2
3
1
2
3
1
2
3
4
5
1
2
S1
Configuration
Dip Switches
J3
No Charging - C
No Charging - N/C
+12VDC Power
Supply
+
DC Output
-
J2
NC
PWR +
PWR -
Connect to chassis GND
at one side ONLY!
485-Com +
485-Com -
Com-Gnd
J9
J12
J13
LAN Card
Connector
Memory Expansion Connector
J14
J4
J5
J6
1
2
3
Note
Com-RTS
Com-CTS
Com-Gnd
RS 485 or
RS 232 Com
Bus Cable
485-Com +, or, Com-TXD
485-Com -, or, Com-RXD
NC
Tamper
Power Fail
Tamper Switch
(In Close Position
when Cabinet Door
Is Closed)
Switch Common
Low Battery - C
Low Battery - N/C
Input ? Common
Input ?
Any Supervised
Input On Any
Adjacent Rack
Mounted Board
(OPTIONAL)
CardRack PWR & Com Harness
Note
PWR +
PWR -
Do NOT tie PWR- to chassis GND !
Port 2
Port 1
Port 3
Connect to chassis GND
at one side ONLY!
8
7
6
5
8
4
3
2
1
Battery
Lithium 3V
PROM
U1
U1 1
Note:
For N-485 Communication Connections, twist the blue pair together and use as the
common; use the orange pair as your data pair, observing polarity. Connect the
external drain shield to the appropriate earth ground on one end.