Honeywell Q682B Owner's Manual - Page 17
Room Temperatures
View all Honeywell Q682B manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 17 highlights
Troubleshooting (continued) Problem Room Temperatures are not correct (continued). Burner-on time too short. Burner-on time too long. No cooling. 1 Check - anticipator setting. (See figure on page 23 for anticipator location.) - anticipator setting. (See figure on page 23 for anticipator location.) - system switch. May be in OFF or HEAT position. - fuse or circuit breaker. Action With system switch at COOL, move temperature setting levers 5°F (3°C) below room temperature. Cooling system should start. If the systems do not operate, call a qualified technician. Increase anticipator setting by 0.05. Observe burner operation. Decrease anticipator setting by 0.05. Observe burner operation. Move switch to COOL position. If fuse is blown or breaker tripped, replace or reset. (continued) 17 69-0574-2