Table 8. Troubleshooting. Continued, Symptom, Possible Cause, Action

Page 18 highlights

TB6575/TB8575 DIGITAL FAN COIL THERMOSTATS Table 8. Troubleshooting. (Continued) Symptom Possible Cause Action Cooling does not turn Cooling equipment failure. For TB6575A/B: on (Cool On is solid in 1. Check for 120/240 Vac at the equipment between power and the display). common, (terminals L and N). 2. Check for 120/240 Vac between the cool (Y) and common (N) terminals. If 120/240 Vac is present, the thermostat is functional. For TB875A: 1. Check for 24 Vac at the equipment on the secondary side of the transformer between power and common (terminals R and C). 2. Check for 24 Vac between the cool terminal (Y) and trans- former common. If 24 Vac is present, the thermostat is func- tional. Loose connection or broken wire between thermostat and cooling equipment. If voltage is present, check the cooling equipment to find the cause of the problem. For TB6575A/B: Check for 120/240 Vac between the cool (Y) and common (N) terminals. For TB875A: Check for 24 Vac between the cool terminal (Y) and transformer common. If voltage is not present, check the wire connection (loose or broken) between the thermostat and the cooling equipment. Fan does not turn on Wiring or connection in a call for Heat. failure Check wiring and make sure the connection is correct. Cannot select fan speed. Fan Control Type selection is incorrect. Check that the Installer Setup code #9 (Fan Control) value is set to zero (0). Heating equipment is Incorrect System Type running in the Cool configured. mode. Check that the Installer Setup code #2 (System Type) value matches the installed heating and/or cooling equipment. Heating equipment does not turn off and heat temperature setting is set below room temperature (Heat On is not in the display). Incorrect System Type configured. Check that the Installer Setup code #2 (System Type) value matches the installed heating and/or cooling equipment. Cannot set the system System Type (Installer setting to Heat. Setup code #2) is set to Cool Only (value = 1). Set the Installer Setup code #2 value to match the installed heating and/or cooling equipment. Cannot set the system System Type (Installer setting to Cool. Setup code #2) is set to Heat Only (value = 0). Set the Installer Setup code #2 value to match the installed heating and/or cooling equipment. Heat On is not in the display. System Type setting is not Set the Installer Setup code #2 to Heat and set the temperature set to Heat and/or the setting above the room temperature. temperature setting is not set above the room temperature. Cool On is not in the display. System Type setting is not Set the Installer Setup code #2 to Cool and set the temperature set to Cool and/or the setting below the room temperature. temperature setting is not set below the room temperature. Remote sensor does Incorrect ISU code. Set the Installer Setup code #4 to Remote (value = 1). not display temperatures Sensor is not compatible. The remote sensor must be TR21 or compatible 20K NTC. Remote Setback does Incorrect ISU code. not activate Make sure the NO/NC and timer selection is correct. Check the value selected for ISU code #19. Remote setpoint error. Make sure the remote setback setpoint is correct for energy saving usage. 62-0311-05 18

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20

TB6575/TB8575 DIGITAL FAN COIL THERMOSTATS
62-0311—05
18
Cooling does not turn
on (Cool On is solid in
the display).
Cooling equipment failure. For TB6575A/B:
1.
Check for 120/240 Vac at the equipment between power and
common, (terminals L and N).
2.
Check for 120/240 Vac between the cool (Y) and common
(N) terminals. If 120/240 Vac is present, the thermostat is
functional.
For TB875A:
1.
Check for 24 Vac at the equipment on the secondary side of
the transformer between power and common (terminals R
and C).
2.
Check for 24 Vac between the cool terminal (Y) and trans-
former common. If 24 Vac is present, the thermostat is func-
tional.
If voltage is present, check the cooling equipment to find the cause
of the problem.
Loose connection or
broken wire between
thermostat and cooling
equipment.
For TB6575A/B:
Check for 120/240 Vac between the cool (Y) and common (N)
terminals.
For TB875A:
Check for 24 Vac between the cool terminal (Y) and transformer
common.
If voltage is not present, check the wire connection (loose or
broken) between the thermostat and the cooling equipment.
Fan does not turn on
in a call for Heat.
Wiring or connection
failure
Check wiring and make sure the connection is correct.
Cannot select fan
speed.
Fan Control Type
selection is incorrect.
Check that the Installer Setup code #9 (Fan Control) value is set to
zero (0).
Heating equipment is
running in the Cool
mode.
Incorrect System Type
configured.
Check that the Installer Setup code #2 (System Type) value
matches the installed heating and/or cooling equipment.
Heating equipment
does not turn off and
heat temperature
setting is set below
room temperature
(Heat On is not in the
display).
Incorrect System Type
configured.
Check that the Installer Setup code #2 (System Type) value
matches the installed heating and/or cooling equipment.
Cannot set the system
setting to Heat.
System Type (Installer
Setup code #2) is set to
Cool Only (value = 1).
Set the Installer Setup code #2 value to match the installed heating
and/or cooling equipment.
Cannot set the system
setting to Cool.
System Type (Installer
Setup code #2) is set to
Heat Only (value = 0).
Set the Installer Setup code #2 value to match the installed heating
and/or cooling equipment.
Heat On is not in the
display.
System Type setting is not
set to Heat and/or the
temperature setting is not
set above the room
temperature.
Set the Installer Setup code #2 to Heat and set the temperature
setting above the room temperature.
Cool On is not in the
display.
System Type setting is not
set to Cool and/or the
temperature setting is not
set below the room
temperature.
Set the Installer Setup code #2 to Cool and set the temperature
setting below the room temperature.
Remote sensor does
not display
temperatures
Incorrect ISU code.
Set the Installer Setup code #4 to Remote (value = 1).
Sensor is not compatible.
The remote sensor must be TR21 or compatible 20K NTC.
Remote Setback does
not activate
Incorrect ISU code.
Make sure the NO/NC and timer selection is correct. Check the
value selected for ISU code #19.
Remote setpoint error.
Make sure the remote setback setpoint is correct for energy saving
usage.
Table 8. Troubleshooting. (Continued)
Symptom
Possible Cause
Action