Honeywell TB6575B1000/U Installation Instructions - Page 8

Vac Wiring Diagrams TB8575

Page 8 highlights

TB6575/TB8575 DIGITAL FAN COIL THERMOSTATS . L W/Y Y/A GI 1 Gm Gh 2 N Rs Sc SB Ps HEAT VALVE COOL VALVE L (HOT) 5 FAN 3 REMOTE SENSOR REMOTE SETBACK N4 1 REMOVE PRE-WIRED WIRE FROM TERMINAL 5 (MID FAN SPEED). 2 JUMPER TERMINALS 5 AND 6 (MID AND HIGH FAN SPEEDS). FAN MEDIUM SETTING WILL OPERATE ON HIGH SPEED. 3 CONNECT TERMINAL 7 TO THE MID FAN SPEED WIRE FROM THE PREVIOUS SYSTEM. 4 REWIRE THE PREVIOUS MID SPEED FAN WIRE TO THE NEUTRAL CIRCUIT IN THE SYSTEM. 5 CHANGE INSTALLER SETUP IS CODE 9 TO 2 FOR 2 SPEED FAN CONTROL. M31328 Fig. 13. Wiring diagram when missing a wire for electromechanical retrofit (120/240 Vac shown). 24 Vac Wiring Diagrams (TB8575) For the TB8575A1000 model, a 24 Vac Class 2 NEMA rated transformer must be used. R W/Y HEAT VALVE Y/A GI Gm FAN L1 Gh 24 VAC (HOT) C L2 1 Rs REMOTE SENSOR Sc SB REMOTE SETBACK Ps 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. M27573 Fig. 14. Two pipes Heat-only wiring diagram (24 Vac shown). R W/Y COOL VALVE Y/A GI Gm FAN L1 Gh 24 VAC (HOT) C L2 1 Rs REMOTE SENSOR Sc SB REMOTE SETBACK Ps 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. M27574 Fig. 15. Two pipes Cool-only wiring diagram (24 Vac shown). R W/Y VALVE Y/A GI Gm FAN L1 Gh 24 VAC (HOT) C L2 1 Rs REMOTE SENSOR Sc SB REMOTE SETBACK Ps 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. M27575 Fig. 16. Two pipes (Heat or Cool) Manual Changeover wiring diagram (24 Vac shown). 62-0311-05 8

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20

TB6575/TB8575 DIGITAL FAN COIL THERMOSTATS
62-0311—05
8
.
Fig. 13. Wiring diagram when missing a wire for
electromechanical retrofit (120/240 Vac shown).
24 Vac Wiring Diagrams (TB8575)
For the TB8575A1000 model, a 24 Vac Class 2 NEMA
rated transformer must be used.
Fig. 14. Two pipes Heat-only wiring diagram (24 Vac
shown).
Fig. 15. Two pipes Cool-only wiring diagram (24 Vac
shown).
Fig. 16. Two pipes (Heat or Cool) Manual Changeover
wiring diagram (24 Vac shown).
M31328
HEAT VALVE
FAN
COOL VALVE
REMOTE SETBACK
REMOTE SENSOR
L (HOT)
3
4
5
5
1
2
1
2
REMOVE PRE-WIRED WIRE FROM TERMINAL 5 (MID FAN SPEED).
JUMPER TERMINALS 5 AND 6 (MID AND HIGH FAN SPEEDS).
FAN
MEDIUM SETTING WILL OPERATE ON HIGH SPEED.
CONNECT TERMINAL 7 TO THE MID FAN SPEED WIRE FROM THE
PREVIOUS SYSTEM.
REWIRE THE PREVIOUS MID SPEED FAN WIRE TO THE NEUTRAL
CIRCUIT IN THE SYSTEM.
CHANGE INSTALLER SETUP IS CODE 9 TO 2 FOR
2 SPEED FAN CONTROL.
3
4
N
L
W/Y
Y/A
GI
Gm
Gh
N
Rs
Sc
SB
Ps
24 VAC
M27573
HEAT VALVE
FAN
L1
(HOT)
L2
1
REMOTE SENSOR
REMOTE SETBACK
1
POWER SUPPLY.
PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
R
W/Y
Y/A
GI
Gm
Gh
C
Rs
Sc
SB
Ps
24 VAC
M27574
COOL VALVE
FAN
L1
(HOT)
L2
1
REMOTE SENSOR
REMOTE SETBACK
1
POWER SUPPLY.
PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
R
W/Y
Y/A
GI
Gm
Gh
C
Rs
Sc
SB
Ps
24 VAC
M27575
VALVE
FAN
L1
(HOT)
L2
1
REMOTE SENSOR
REMOTE SETBACK
1
POWER SUPPLY.
PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
R
W/Y
Y/A
GI
Gm
Gh
C
Rs
Sc
SB
Ps