Honeywell TB6575B1000/U Installation Instructions - Page 2

Specifications - thermostat

Page 2 highlights

TB6575/TB8575 DIGITAL FAN COIL THERMOSTATS SPECIFICATIONS Supply Voltages: TB6575A1000 and TB6575B1000: • 120 Vac ±10% at 50/60Hz • 240 Vac ±10% at 50/60Hz TB8575A1000: • 20 to 30 Vac at 50/60Hz (using 24 Vac, Class 2, NEMA rated transformer) Safety Fuse: 15 A, 250 Vac. If the safety fuse blows, the thermostat must be replaced. The fuse is not field replaceable. Electrical Ratings: (see Table 1). Table 1. Electrical Ratings. Component Amps (inductive) for: 24 Vac 120 Vac 240 Vac Fan Relay Heat/Cool Relay 1.0 A 1.0 A 6.0 A 1.0 A 3.0 A 1.0 A Environmental Ratings: Temperature: Operating Range: 18°C to 49°C (0°F to 120°F). Shipping and Storage Range: -29°C to 49°C (-20°F to 120°F). Humidity: 5% to 90% RH, non-condensing. Onboard Temperature Sensor: Type: 10K NTC Working Range: 18°C to 49°C (0°F to 120°F) Display Range: 0°C to 37°C (32°F to 99°F) Accuracy ±2.0°F at 70°F Remote Temperature Sensor (optional): Type: 20K NTC Working Range: 18°C to 49°C (0°F to 120°F) Display Range: 0°C to 37°C (32°F to 99°F) Accuracy ±2.0°F at 70°F Remote Pipe Sensor (optional): Type: 20K NTC Working Range: 0°C to 93°C (32°F to 199°F) Display Range: 0°C to 93°C (32°F to 199°F) Accuracy ±5.0°F over the temperature sensing range Remote Setback Input: Dry contact, maximum resistance of 100 ohms. TB6575 - 9Vdc, < 4 mA; TB8575 - 16 Vdc, < 5 mA. Note Electrical WARNING on page 3. Remote Setback Range: Heating: 10°C to 21°C (50°F to 70°F). Cooling: 22°C to 32°C (72°F to 90°F). Enclosure: Plastic (cover, sub-base, and optional adaptor plate) Junction Box Mounting: Direct mounting on a horizontal single gang NEMA 2 x 4 in. surface mount electrical box, or on 4 x 4 in. box or vertical 2 x 4 in. surface mount electrical box with the optional 50033847-001 adapter plate. Dimensions: See Fig. 1 on page 3. Wiring: 11 screw-in terminals located on the sub-base capable of accepting up to 2 x 18 AWG (0.8 sq. mm), 1 x 16 AWG (1.3 sq. mm), or 1 x 14 AWG (2.1 sq. mm) wires. Accepts stranded or unstranded 14-28 gauge wire. NOTES: 1. The TB6575A1000 model is pre-fitted with colorcoded fly leads (16 AWG) attached to seven terminals. 2. The TB6575B1000 model is pre-fitted with colorcoded fly leads (16 AWG) attached to six terminals. 3. The TB8575A1000 model does not have fly leads attached to any terminals. 4. See Table 3 on page 5 for fly lead usage. Minimum Operational Life (at maximum load): Thermostat contacts: 100,000 cycles Approvals: CSA Certified C/US for Canada and the U.S.A. Meets the same requirements as UL-873. FCC Part 15 Class B Accessories: • 50033847-001 - Adapter plate for mounting on a vertical 2 x 4 in. single-gang or double-gang NEMA standard vertical switch box (6 1/4 in. (158 mm) x 5 1/ 16 in. (128 mm) x 13/22 in. (10 mm)). • TR21 - 20K Ohm NTC Non-Linear Remote temperature sensor. Other acceptable remote temperature sensors are - • 20K Ohm: C7041B2005, C7041B2013, C7041C2003, C7041P2004, C7770A1006, C7772A1004, and C7772A1012 • 10K Ohm (for averaging only): TR21-A • PS20 - Remote pipe sensor (20K Ohm) • W6380B1005 - Fan Coil Unit Relay Control Center • WSK-24 - Wireless Occupancy Solution (Receiver, occupancy sensor and door sensor) Models, applications, and features: Table 2 identifies the applications and features of each model. Table 2. Applications and Features Applications Models Heat/Cool/ Pipes Voltage Auto TB6575A1000 All 2 or 4 120 or 240 Vac TB6575B1000 Heat or 2 Cool 120 or 240 Vac TB8575A1000 All 2 or 4 24 Vac Features Number Energy Fan: On, Manual/ Remote Back of Relaysa Savings Auto, or Auto Sensor Light Input 3 speed Changeover 5 Yes Yes Yes Yes Yes 4 5 Pipe Sensorb Yes 62-0311-05 2

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20

TB6575/TB8575 DIGITAL FAN COIL THERMOSTATS
62-0311—05
2
SPECIFICATIONS
Supply Voltages:
TB6575A1000 and TB6575B1000:
120 Vac ±10% at 50/60Hz
240 Vac ±10% at 50/60Hz
TB8575A1000:
20 to 30 Vac at 50/60Hz (using 24 Vac, Class 2,
NEMA rated transformer)
Safety Fuse:
15 A, 250 Vac. If the safety fuse blows, the
thermostat must be replaced. The fuse is not field
replaceable.
Electrical Ratings:
(see Table 1).
Environmental Ratings:
Temperature:
Operating Range: 18°C to 49°C (0°F to 120°F).
Shipping and Storage Range: -29°C to 49°C (-20°F to
120°F).
Humidity:
5% to 90% RH, non-condensing.
Onboard Temperature Sensor:
Type: 10K NTC
Working Range: 18°C to 49°C (0°F to 120°F)
Display Range: 0°C to 37°C (32°F to 99°F)
Accuracy ±2.0°F at 70°F
Remote Temperature Sensor (
optional
):
Type: 20K NTC
Working Range: 18°C to 49°C (0°F to 120°F)
Display Range: 0°C to 37°C (32°F to 99°F)
Accuracy ±2.0°F at 70°F
Remote Pipe Sensor (
optional
):
Type: 20K NTC
Working Range: 0°C to 93°C (32°F to 199°F)
Display Range: 0°C to 93°C (32°F to 199°F)
Accuracy ±5.0°F over the temperature sensing range
Remote Setback Input:
Dry contact, maximum
resistance of 100 ohms. TB6575 – 9Vdc, < 4 mA; TB8575
– 16 Vdc, < 5 mA. Note Electrical WARNING on page 3.
Remote Setback Range:
Heating: 10°C to 21°C (50°F to 70°F).
Cooling: 22°C to 32°C (72°F to 90°F).
Enclosure:
Plastic (cover, sub-base, and optional adap-
tor plate)
Junction Box Mounting:
Direct mounting on a horizontal
single gang NEMA 2 x 4 in. surface mount electrical box,
or on 4 x 4 in. box or vertical 2 x 4 in. surface mount
electrical box with the optional 50033847-001 adapter
plate.
Dimensions:
See Fig. 1 on page 3.
Wiring:
11 screw-in terminals located on the sub-base
capable of accepting up to 2 x 18 AWG (0.8 sq. mm), 1 x
16 AWG (1.3 sq. mm), or 1 x 14 AWG (2.1 sq. mm) wires.
Accepts stranded or unstranded 14-28 gauge wire.
NOTES:
1.
The TB6575A1000 model is pre-fitted with color-
coded fly leads (16 AWG) attached to seven
terminals.
2.
The TB6575B1000 model is pre-fitted with color-
coded fly leads (16 AWG) attached to six
terminals.
3.
The TB8575A1000 model does not have fly
leads attached to any terminals.
4.
See Table 3 on page 5 for fly lead usage.
Minimum Operational Life (at maximum load):
Thermostat contacts: 100,000 cycles
Approvals:
CSA Certified C/US for Canada and the U.S.A. Meets
the same requirements as UL-873.
FCC Part 15 Class B
Accessories:
50033847-001 – Adapter plate for mounting on a
vertical 2 x 4 in. single-gang or double-gang NEMA
standard vertical switch box (6 1/4 in. (158 mm) x 5 1/
16 in. (128 mm) x 13/22 in. (10 mm)).
TR21 – 20K Ohm NTC Non-Linear Remote
temperature sensor.
Other acceptable remote temperature sensors are —
20K Ohm: C7041B2005, C7041B2013, C7041C2003,
C7041P2004, C7770A1006, C7772A1004, and
C7772A1012
10K Ohm (for averaging only): TR21-A
PS20 – Remote pipe sensor (20K Ohm)
W6380B1005 – Fan Coil Unit Relay Control Center
WSK-24 - Wireless Occupancy Solution (Receiver,
occupancy sensor and door sensor)
Models, applications, and features:
Table 2 identifies the applications and features of each
model.
Table 2. Applications and Features
Table 1. Electrical Ratings.
Component
Amps (inductive) for:
24 Vac
120 Vac
240 Vac
Fan Relay
1.0 A
6.0 A
3.0 A
Heat/Cool Relay
1.0 A
1.0 A
1.0 A
Models
Applications
Features
Heat/Cool/
Auto
Pipes
Voltage
Number
of Relays
a
Energy
Savings
Input
Fan: On,
Auto, or
3 speed
Manual/
Auto
Changeover
Remote
Sensor
Back
Light
Pipe
Sensor
b
TB6575A1000
All
2 or 4
120 or
240 Vac
5
Yes
Yes
Yes
Yes
Yes
Yes
TB6575B1000
Heat or
Cool
2
120 or
240 Vac
4
TB8575A1000
All
2 or 4
24 Vac
5