Kenmore 33176 Owners Manual - Page 11
itdoesnotsag,thereby
View all Kenmore 33176 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 11 highlights
DonotcovetrheinstructiomnanuaKl.eepit onthesideof thewatehr eateorrnearbfyorfuturereference. Doobtain ewwarninagndinstructiolanbelfsromSearfsor placemeonnt theblankedtirectloyvertheexistinlgabels. Doinspectht einsulatiobnlankefrtequenttloymakecertain it doesnotsag,thereboybstructincogmbustioanirflow. B. ALL AIR FROM OUTDOORS: (See Figures 9, 11,12 and 13) The confined space shall be provided with two permanent openings, one commencing within 12 inches (30 cm) of the top and one commencing within 12 inches (30 cm) from the bottom of the enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. Combustion Air and Ventilation for Appliances Located in Unconfined Spaces CHIMNEY OR GAS VENT VENTiLATiON LOUVERS (EACH END OF ATTIC) UNCONFINED SPACE is space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m 3 per kW) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed, through openings not furnished with doors, are considered a part of the unconfined space. In unconfined spaces in buildings, infiltration may be adequate to provide air for combustion, ventilation and dilution of flue gases. However, in buildings of tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.), additional air may need to be provided using the methods described in Combustion Air and Ventilation for Appliances Located in Confined Spaces. Combustion Air and Ventilation for Appliances Located in Confined Spaces CONFINED SPACE is a space whose volume is less than 50 cubic feet per 1,O0O Btu per hour (4.8 m 3 per kW) of the aggregate input rating of all appliances installed in that space. A. ALLAIR FROM INSIDE BUILDINGS: (See Figure 9 and Figure 10) The confined space shall be provided with two permanent openings communicating directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space. The total input of all gas utilization equipment installed in the combined space shall be considered in making this determination. Each opening shall have a minimum free area of one square inch per 1,000 Btu per hour (22 cm2/kW) of the total input rating of all gas utilization equipment in the confined space, but not less than 100 square inches (645 cm2). One opening shall commence within 12 inches (36 cm) of the top and one commencing within 12 inches (30 cm) of the bottom of the enclosures. NT OUTLET AIR "WATERNEATER FURNACE ,INLET _R DUCT ALT. INLET AIR VENTILATION LOUVERS FIGURE 11. When directly communicating with the outdoors, each opening shall have a minimum free area of 1 square inch per 4,000 Btu per hour (5.5 cm2/kW) of total input rating of all equipment in the enclosure, see Figure 12. VENTILATION LOUVERS EACH END OF ATTIC) FURNACE -- INLET AIR DUCT (ENDS I'OR 30 crn ABOVE FLOOR) FIGURE 12. When communicating with the outdoors through vertical ducts, each opening shall have a minimum free area of 1 square inch per 4,000 BTU per hour (5.5 cm2/kW) of total input rating of all equipment in the enclosure, see Figure 12 on page 11. When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch per 2,000 BTU per hour (11 cm2/kW) of total input rating of all equipment in the enclosure, see Figure 14. FURN_A_CE _ HWE_ _ OPENINGS FIGURE 10, Alternatively a single permanent opening may be used when communicating directly with the outdoors, or with spaces that freely communicate with the outdoors. The opening shall have a minimum free area of 1 square inch per 3,006 BTU per hour (8.3 cm2/kW) of total input rating of all equipment in enclosure. See Figure 13. 11