Kenmore 33205 Owners Manual - Page 12

uzooo

Page 12 highlights

Chemicvalpocrorrosiofntheflueb, lowearssembalnydvenstystem 3. When communicating with the outdoors through horizontal ducts, mayoccuifrairforcombustcion taicnesrtacinhemicvalporSs.pray each opening shall have a minimum free area of 1 square inch per canpropellanctlse,aninsgolventrse,frigeraatonrdairconditioner 2,000 Btu per hour (11 cm2/kW)) of total input rating of all equipment refrigeranstwsi,mmipnogocl hemicaclas,lciumandsodiumchloride, in the enclosure, see Figure 14. waxebs,leacahndprocescshemicaalrsetypicaclompounwdhsich arepotentiaclolyrrosive. 4. When ducts are used, they shall be of the same cross-sectional area A. ALL AIR FROM INSIDE BUILDINGS: (See Figure 10 and 11) as the free area of the openings to which they connect. The minimum The confined space shall be provided with two permanent openings communicating directly with an additional room(s) of sufficient volume short side dimension of rectangular air ducts shall not be less than 3 inches (7.6 cm), see Figure 14. so that the combined volume of all spaces meets the criteria for an unconfined space. The total input of all gas utilization equipment VENTTHROUGH installed in the combined space shall be considered in making this determination. Each opening shall have a minimum free area of one _ROOF "% square inch per 1,000 Btu per hour (22 cm2/kW) of the total input rating of all gas utilization equipment in the confined space, but not less than 100 square inches (645 cm2). One opening shall commence within 12 inches OUTLET AIR DUCT ! VENT TO OUTDOORS (31 cm) of the top and one commencing within 12 inches (31 cm) of the bottom of the enclosures. € o I INLET A_R DUCT !, VENT THROUGH =_. _ ROOF [_ _1 OPENINGS _ _ VENT TO _UTDOORS W'ATER {_ FIGURE 14. FIGURE 11. B. ALL AIR FROM OUTDOORS: (See Figures 12, 13 and 14) The confined space shall be provided with two permanent openings, one commencing within 12 inches (31 cm) of the top and one commencing within 12 inches (31 cm) from the bottom of the enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. 1. When directly communicating with the outdoors, each opening shall have a minimum free area of 1 square inch per 4,000 Btu per hour (5.5 cm2/kW) of total input rating of all equipment in the enclosure, see Figure 12. VENTILATION LOUVERS (each end of attic VENT THROUGH ROOF VENT TO OUTDOORS FIGURE 14A. 5. Alternatively a single permanent opening may be used when communicating directly with the outdoors, or with spaces that freely communicate with the outdoors. The opening shall have a minimum free area of 1 square inch per 3,000 BTU per hour (8.3 cm2/kW) of total input rating of all equipment in the enclosure. See Figure 14A. VENTILATION LOUVERS leach end of attic)_,_.. VENTILATION LOUVERS FIGURE 12. VENT THROUGH AIR OUTLET _-_It _ VENT TO lii1-4u4z.o0oo INLEkTmRDUCT-"_ _I I H_WATER lends 1" above floor) nuL_ n HEATER FIGURE 13. 6. Louvers and Grilles: In calculating free area, consideration shall be given to the blocking effect of louvers, grilles or screens protecting openings. Screens used shall not be smaller than 1/4 inch (6.4 mm) mesh. If the free area through a design of louver or grille is known, it should be used in calculating the size opening required to provide the free area specified. If the design and free area is not known, it may be assumed that wood louvers will be 20-25 percent free area and metal louvers and grilles will have 60-75 percent free area. Louvers and grilles shall be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment operation. 7. Special Conditions Created by Mechanical Exhausting or Fireplaces: operation of exhaust fans, ventilation systems, clothes dryers or fireplaces may create conditions requiring special attention to avoid unsatisfactory operation of installed gas utilization equipment. 2. When communicating with the outdoors through vertical ducts, each opening shall have a minimum free area of 1 square inch per 4,000 Btu per hour (5.5 cm2/kW) of total input rating of all equipment in the enclosure, see Figure 13. 12

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36

Chemical
vapor
corrosion
ofthe
flue,
blower
assembly
andvent
system
mayoccur
ifairforcombustion
contains
certain
chemical
vapors.
Spray
canpropellants,
cleaning
solvents,
refrigerator
andairconditioner
refrigerants,
swimming
pool
chemicals,
calcium
andsodium
chloride,
waxes,
bleach
andprocess
chemicals
are
typical
compounds
which
arepotentially
corrosive.
A. ALL AIR FROM
INSIDE
BUILDINGS:
(See Figure
10 and 11)
The confined
space
shall
be
provided
with
two
permanent
openings
communicating
directly with
an additional
room(s)
of sufficient
volume
so that
the combined
volume
of all spaces
meets
the criteria
for an
unconfined
space.
The
total
input
of all gas
utilization
equipment
installed
in the
combined
space
shall
be considered
in making
this
determination.
Each opening
shall have a minimum
free area of one
square
inch per 1,000 Btu per hour (22 cm2/kW) of the total input rating of
all gas utilization
equipment
in the confined
space, but not less than 100
square
inches (645 cm2). One opening
shall commence
within
12 inches
(31 cm) of the top and one commencing
within
12 inches (31 cm) of the
bottom of the enclosures.
VENT
THROUGH
=_.
_
ROOF
[_
_
VENT
TO
_1
_UTDOORS
OPENINGS
_
W'ATER
{_
FIGURE
11.
B. ALL AIR FROM
OUTDOORS:
(See Figures
12, 13 and
14)
The confined
space
shall be provided
with two
permanent
openings,
one
commencing
within
12
inches
(31
cm)
of
the
top
and
one
commencing
within
12 inches (31 cm) from the bottom of the enclosure.
The openings
shall communicate
directly, or by ducts, with the outdoors
or spaces
(crawl or attic) that freely communicate
with the outdoors.
1.
When directly communicating
with the outdoors,
each opening
shall
have a minimum
free area of 1 square
inch per 4,000
Btu per hour
(5.5
cm2/kW) of total input rating of all equipment
in the enclosure,
see Figure
12.
VENTILATION
LOUVERS
(each
end of attic
VENT
THROUGH
ROOF
VENT
TO
OUTDOORS
3.
4.
5.
When
communicating
with the
outdoors
through
horizontal
ducts,
each opening
shall have a minimum
free area of 1 square
inch per
2,000 Btu per hour (11 cm2/kW)) of total input rating of all equipment
in the enclosure,
see Figure
14.
When ducts are used, they shall be of the same cross-sectional
area
as the free area of the openings
to which
they connect.
The minimum
short
side dimension
of rectangular
air ducts shall
not be less than
3 inches
(7.6 cm), see Figure
14.
o
OUTLETAIRDUCT
!
I
INLET
A_R
DUCT
!,
VENTTHROUGH
_ROOF
"%
VENT
TO
OUTDOORS
FIGURE
14.
FIGURE
14A.
Alternatively
a single
permanent
opening
may
be
used
when
communicating
directly with the outdoors,
or with spaces
that freely
communicate
with the outdoors.
The opening
shall have a minimum
free area of 1 square
inch per 3,000
BTU per hour (8.3 cm2/kW) of
total input rating of all equipment
in the enclosure.
See Figure
14A.
VENTILATION
LOUVERS
FIGURE
12.
VENTILATION
LOUVERS
leach
end of attic)_,_..
VENT
THROUGH
AIR OUTLET
_-_It
_
VENT
TO
lii
1-44.0
uzooo
INLET
kmRDUCT-"__I
IH_WATER
lends
1" above
floor)
n
uL_
n
HEATER
::::::::::::::::::::::
FIGURE
13.
2.
When communicating
with the outdoors
through
vertical
ducts, each
opening
shall have a minimum
free area of 1 square
inch per 4,000
Btu per hour (5.5 cm2/kW) of total input rating of all equipment
in the
enclosure,
see Figure
13.
6.
7.
12
Louvers
and Grilles:
In calculating
free area, consideration
shall be
given
to the blocking
effect of louvers,
grilles or screens
protecting
openings.
Screens
used
shall
not
be
smaller
than
1/4
inch
(6.4 mm) mesh.
If the free area through
a design
of louver or grille
is known, it should
be used in calculating
the size opening
required
to provide the free area specified.
If the design
and free area is not
known, it may be assumed
that wood
louvers will be 20-25
percent
free
area
and
metal
louvers
and
grilles
will
have
60-75
percent
free area.
Louvers
and grilles shall be fixed
in the open position
or
interlocked
with the equipment
so that they are opened automatically
during
equipment
operation.
Special Conditions
Created
by Mechanical
Exhausting
or Fireplaces:
operation
of exhaust
fans,
ventilation
systems,
clothes
dryers
or
fireplaces
may create conditions
requiring
special
attention
to avoid
unsatisfactory
operation
of installed
gas utilization
equipment.